3 Operation
3.3 Configuring Mode (Parameterization and Configuring Mode)
3.3.2 Parameterization Mode AdAP (Adaptation)
SIP ART DR24 6DR2410
C79000-G7476-C153-03
139
The error message flashes on dd1 and dd2 when adaptation is aborted. The error messages
are acknowledged with the Enter key (see figure 3-7, page 142).
D Pre adaptation
The data source AdAP is low and may display readiness for adaptation when connected, for
example with L13. First the parameters for the presettings (tU, dPv, dY) are displayed. They
must be set according to the desired jump signal. Then the old parameters xx.o with the ID Pi
or Pid with their value and the new parameters xx.n with the ID Strt AdAP appear on the dis-
plays. The old and the new parameters are not adjustable.
The adaptation can only be started with the Enter key (tA4) when the new parameters
**
.n with the display Strt AdAP are selected (manual operation is a prerequisite).
D During adaptation
The data source AdAP switches alternately between high and low and may display the current
adaptation when connected for example with L3. The process can be monitored on the com-
pletely connected process display.
D Aborted adaptation
The data source AdAP is low and may display readiness for adaptation after error acknowl-
edgement when connected for example with L3. The current adaptation can be aborted manu-
ally or automatically by the error monitor.
Manual abortion can be activated in the event of danger by pressing the Exit key (tA1). It then
returns to the selection mode after AdAP. From there you can return to the process operation
mode by pressing the Exit key (tA1) again. The controller is in manual mode and the manual
manipulated variable can be adjusted if wired appropriately.
Automatic abortion is effected by the error monitors (see table 3--2, page 143). The error mes-
sages are displayed on dd1 and dd2. The error message is acknowledged by pressing the En-
ter key (tA4), the parametering mode AdAP is retained, tU is displayed, the defaults can be cor-
rected if necessary. Abortion by the control signals N and yBL can be prevented by
appropriate connection (locking with controller output AL).
D Post adaptation
The data source AdAP is high and may display the end of adaptation when connected for ex-
ample with L3. The parameters
**
.o with the ID Pi or Pid and the new parameters
**
.n with the
ID Pi.1 to 8 and Pid.1 to 8 for Pi and Pid controller design are offered. The digits after the Pi or
Pid ID indicate the line order .
The old and the new parameters are adjustable.
On pressing the Exit key (tA1) the parameters
**
.o or
**
.n which have just been selected are
transfered to AdAP when returning to the parameter preselection mode. The data source AdAP
is now set to low. When transfering
**
.o, these parameters remain unchanged if they have not
been changed manually. When transfering
**
.n the old parameters are overwritten by the new