Manual
1 Technical Description
1.4 Function Principle
1.4.2 Description of the Option Module
SIP ART DR24 6DR2410
C79000-G7476-C153-03
17
-- Interface on
-- Even parity
-- LRC without
-- Baud rate 9600
-- Parameters/process values writable (as desired)
-- Station number according to selection 0 to 125
Make sure that the station number is not assigned double on the bus. The PROFIBUS module
serves to connect the SIPART controllers to a master system for operating and monitoring. In
addition the parameters and configuring switches of the controller can be read and written. Up
to 32 process variables can be selected and read out cyclically by configuration of the PROFI-
BUS module.
The process data are read out of the controller in a polling procedure with an update time
< 300 ms. If the master writes process data to the slave, these become active after a maximum
1 controller cycle.
A technical description including the controller base file (*.GSD) is available for creating a mas-
ter--slave linking software for interpreting the identifications and useful data from and to the
SIPART controller.
The discription and the GSD file can be downloaded from the INTERNET.
www.siemens.com/sipartdr
The programs SIPART S5 DP and S7 DP are offered for certain hardware configurations.
Controller base file and type file, general
The controller base file (GSD file) is necessary for connecting the controllers SIPART DR to any
remote systems.
The type file is required at present when connecting to a CPU of the SIMATIC S5/S7.
The DP master connection is parameterized with these files.
6DR2803-8C Serial interface RS 232/RS 485
D Serial interface for RS 232 or RS 485 with electrical isolation
Canbeinsertedinslot4.
For connecting the controller SIPART DR24 to a master system for operating and monitoring.
All process variables can be sent, the external setpoint, tracking variable, operating modes, pa-
rameters and configurations sent and received.
The interface traffic can take place as follows:
RS 232
As point-to-point connection
SIPART Bus
The SIPART bus driver is no longer available.
Therefore, please realize multi--couplings via RS 485 or PROFIBUS DP.
RS 485
As a serial data bus w ith up to 32 users.