Configure doors 
26 
Building Technologies  052_SiPass_Entro_6_5_A24205-A335-B318_e_en
Fire Safety & Security Products    10.03.2010
11.2  Setting properties 
1.  Open Entro [ 13] application and click the Doors tab. 
Since the installer has already allocated addresses for the doors they are also 
registered with a name in the system. 
2.  Select the name (by clicking it) of the door whose information you want to 
enter. 
3.  Click Edit.  
4.  The name of the door is displayed in the Name field. 
5.  Enter the desired maximum unlocking time in the Unlock time field. Click the 
up- or down arrow respectively to increase or decrease the value, or enter the 
desired value in the field directly.  
The time available to open the door after a valid card has been swiped and/or a 
valid PIN has been entered. If the door is not opened during this time, it is 
locked again. Recommended opening time is 5 seconds. You can choose an 
unlock time between 1 and 99 seconds. 
6.  Enter the desired maximum Opening time. This is the time the door can be 
open before the warning signal starts (a buzzer and/or warning relay). You can 
choose an opening time between 1 and 999 seconds. 
7.  Enter the door held warning time in the Door held open warning time field. Click 
the up- or down arrow respectively to increase or decrease the value, or enter 
the desired value in the field directly. 
If the door is still open when the opening time is over, a buzzer sounds at the 
door for the time set as door held warning time. The buzzer reminds the person 
entering to close the door immediately as an alarm is about to go off. 
Recommended door held warning time is 20 seconds. You can choose a time 
between 1 and 99 seconds. 
8.  In the Time schedule field, choose the time schedule applying to the door. Click 
the down arrow to display a list of available time schedules (the time schedules 
you registered earlier). You can also click on the clock icon to 
Create
, 
Edit
 or 
Copy
 a time schedule. Then choose the desired time schedule by clicking the 
name. 
9.  Choose security levels for the different time zones in the time schedule. Click 
the down arrow to display a list of available security levels. Then choose the 
desired security level by clicking the name. 
10. Choose the suitable security level to apply to the reader in off-line condition 
(e.g. during a communications breakdown) in the same way. Persons 
belonging to the Priority group are the only ones that can open doors in an off-
line condition. This is only true of doors where the PD30-EM, PD40-EM, DC22 
or DC12 door controllers with additional readers are installed. 
11. Click the Advanced tab.  
12. Enter the choices you have made for the door concerning access registration, 
remote opening (exit request) and background lighting. 
13. If you are using a motor lock, select which time zones the motor lock should be 
unlocked.