External Tripping Busbar Section (Direct)
Setting Values
Supervision Time 0.00 s to 60.00 s Increments of 0.01 s
Operate Time
Minimum operate time High speed relay (type HS) approx. 4 ms
Fast relay (type F) approx. 8 ms
Tolerance
Process tolerance for the supervision time 1 % of the setting value or 10 ms
11.8
Technical Data
11.8 External Tripping Busbar Section (Direct)
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 571
C53000-G5040-C019-6, Edition 06.2016