CFC
Typical response times and maximum number of ticks of the CFC task levels:
Task Level Time (in ms) Ticks CP200 Ticks CP300
Fast Event-Trig-
gered
<1 500 1000
Event-Triggered
<10 13 254 15 359
Interlocking
<10 128 873 in total 149 603 in total
Measurement
250
The times describe the response time of a typical CFC chart at the respective task level. The maximum number
of ticks applies to a typical load for the device based on the application template Basics.
The task level Measurement runs in cycles every 500 ms. All other task levels are event-triggered.
In order to estimate the tick consumption of a CFC chart, you can use the following formula:
T
chart
= 5 ∙ n
Inp
+ 5 ∙ n
Outp
+ T
TLev
+ ∑
i
T
int
+ ∑
j
T
Block
where:
n
Inp
Number of indications routed as input in the CFC chart
n
Outp
Number of indications routed as output in the CFC chart
T
TLev
101 Ticks in Fast Event-Triggered Level
104 Ticks in Event-Triggered Level
54 Ticks in Measurement Level
74 Ticks in Interlocking Level
T
int
Number of internal connections between 2 CFC blocks in one chart
T
Block
Used ticks per CFC block (see Technical Data)
Table 11-3 Ticks of the Individual CFC Blocks
Element Ticks
ABS_D 2.3
ABS_R 1.5
ACOS_R 6.9
ADD_D4 3.4
ADD_R4 3.3
ADD_XMV 6.4
ALARM 1.8
AND_SPS 1.1
AND10 2.9
APC_DEF 1.2
APC_EXE 1.0
APC_INFO 3.9
ASIN_R 1.3
ATAN_R 1.2
BLINK 1.3
BOOL_CNT 2.0
BOOL_INT 1.5
BSC_DEF 1.3
BSC_EXE 1.1
BSC_INFO 2,7
11.38
Technical Data
11.38 CFC
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual 621
C53000-G5040-C019-6, Edition 06.2016