Parameters and properties
37
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
2.4 Annunciations to the PROFIBUS-DP master
Protection pickup Protection annunciations which indicate the status “Protection pickup” are
active only for the period of time of the protection pickup.
Protection TRIP The parameter Minimum Duration of TRIP Command (parameter address = 210)
allows setting of the minimum duration of the TRIP command.
This time setting applies to all protection functions which may cause a TRIP signal.
After a protection TRIP, the corresponding protection annunciations transmit the value
ON for the programmed minimum time duration.
Note:
When analysing the annunciations of the SIPROTEC device in the PROFIBUS-DP
master, it should be noted that due to the cycle period of the PROFIBUS-DP system
or due to the cyclic processing time of a PLC, temporary changes of an annunciation's
value (ON and OFF within one cycle) may eventually not be recognized.
This applies in the first place for protection annunciations.

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals