PROFIBUS-DP - Parameterization in DIGSI
68
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
Change of an
existing allocation
If an information already routed on system interface shall get another (empty) position
in the PROFIBUS-DP message, then the Object properties dialog window (ref.
to Figure 4-6) has to be selected (Properties ... in the pop-up menu when press-
ing the right mouse button in one of the columns "Display text", "Long text" or "Type"
of the DIGSI Configuration matrix in the row which is associated to the infor-
mation).
Depending on the information type the following parameters are to select in the prop-
erty sheet Protocol info source or Protocol info destination of the
Object properties dialog window:
Attention!
The information type of double commands for routing as "Source system interface"
depends on the information type of the associated checkback indication.
Only double commands with a double-point indication as checkback indication can
be routed to the positions in the PROFIBUS-DP message which are reserved for
double commands according to the bus mapping.
Double commands with a single-point indication as checkback indication or without
checkback indication are treated via PROFIBUS-DP like single commands and
must be routed to the positions reserved for single commands.
Commands without checkback indication can not be routed to “Destination system
interface”. Reading the state of these command types is not possible via PROFI-
BUS-DP.
Parameter Comments
Info types for
Protocol info
source
Info types for
Protocol info
destination
Byte offset The offset indicates the byte in the
PROFIBUS-DP message in which the
bit value is placed.
IntSP, IntDP,
SC/DC, SF/DF
SP, DP, Out,
IntSP, IntDP
The offset indicates the byte position in
the PROFIBUS-DP message.
-TxTap
The offset indicates the beginning of the
most significant byte in the message.
- MV, MVMV,
PMV
Bit mask In the bit mask value all bit positions are
set to 1 which are associated to the in-
formation.
Representation of the bit mask as
decimal number in DIGSI 4.21,
hexadecimal number from DIGSI 4.3.
IntSP, IntDP,
SC/DC, SF/DF
SP, DP, Out,
IntSP, IntDP

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals