Technical data
87
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
Example Redundant optical ring with nine SIPROTEC devices (with optical communication mo-
dules) and one OLM/G12 for the connection of the PROFIBUS-DP master.
Bild 5-1 PROFIBUS parameterization - Number of OLM
Note:
The PSO module is configured to communicate in a redundant optical ring (two fibre
ring) in OLM V2 mode by default.
For an OLM/S4 or OLM/G12 (in compatibility mode) used within such a ring topology
this corresponds to the following DIL switch settings:
OLM/S4
S1 (Mode) = 0,
S2 (Redundancy) = 1 and
S5 (Opt. Power/Dist.) = 0
OLM/G12 (in compatibility mode, S7 = 1)
S1 (Mode) = 0,
S2 (Redundancy) = 1 and
S3 (Distance) = 1
Please note for parameterization of a PROFIBUS-DP communication with re-
dundant optical ring topology:
every optical SIPROTEC communication module (PSO module) contains an OLM,
the parameters “Retry limit” and “Slot time (t
slot
)” have to be set to correct values in
the PROFIBUS-DP master.
Set “Retry limit” at least equal to 3.
You get the correct value for “Slot time” if you enter for “Number of OLM” in the
Network settings in the parameterization system of the PROFIBUS-DP master
the number of OLM/S4 or OLM/G12 devices plus the number of connected opti-
cal communication modules of the SIPROTEC devices.

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals