SIRIUS 3RU2/3RB3 overload relays 
  5.5 Configuration 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
507 
Ambient temperatures for 3RU21 overload relays  
3RU21 thermal overload relays compensate temperature in the temperature range from –
40 °C to +60 °C according to IEC/EN 60947-4-1. At temperatures from +60 °C to +80 °C, the 
upper set value of the setting range has to be reduced by a specific factor in accordance with 
the table below. 
Table 5- 11  Ambient temperature for 3RU21 overload relays 
Reduction factor for the upper set value 
Ambient temperature in °C 
Current ranges 
0.11 to 20 A 
Current ranges 17 to 40 
A 
+60  1.0  1.0 
+65  0.87  0.97 
+70  0.94  0.94 
+75  0.81  0.90 
+80  0.73  0.86 
Ambient temperatures for 3RB30/3RB31 overload relays  
3RB30/3RB31 solid-state overload relays compensate temperature in the temperature range 
from –25 °C to +60 °C according to IEC/EN 60947-4-1.  
The reduction factors which have to be taken into account when using solid-state overload 
relays at an ambient temperature higher than 60°C can be obtained on request from our 
Technical Assistance on the Internet (http://www.siemens.com/automation/service&support
). 
Derating during heavy-duty starting for 3RB30/3RB31 overload relays  
There is no derating during heavy-duty starting in size S00 (up to 16 A). 
The following derating has to be taken into account in size S0 (up to 40 A). 
Table 5- 12  Derating during heavy-duty starting, 3RB30/3RB31 overload relays 
CLASS  Rated current 
CLASS 20  I
e max 
= 32 A 
CLASS 30  I
e max 
= 25 A 
Special application environments 
SIRIUS components have been approved by a whole range of bodies for various sectors 
(shipbuilding, etc.). An up-to-date list of approvals appears in Chapter 20 of the Siemens 
Low Voltage LV1 Catalog, and more information, as well as an option to download 
certificates, can be obtained on the Internet 
(http://www.siemens.com/automation/service&support
).