SIRIUS 3RU2/3RB3 overload relays 
  5.10 Technical data 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
547 
Type  3RB30 1., 3RB31 1.  3RB30 2., 3RB31 2. 
Size  S00  S0 
Width  45 mm  45 mm 
Repeat terminals  
  Coil repeat terminal 
Yes  Not required 
  Auxiliary switch repeat terminal 
Yes  Not required 
Degree of protection acc. to IEC 60529  IP20 
Touch protection acc. to IEC 61140  Finger-safe 
Shock resistance with sine 
acc. to IEC 60068-2-27 
g/ms  15 / 11
2)
 
Electromagnetic compatibility (EMC) -  Immunity  
  Conducted interference suppression 
- Burst acc. to 
IEC 61000-4-4  
(corresponds to 
severity 3) 
kV  2 (power ports), 1 (signal ports)  
- Surge acc. to 
IEC 61000-4-5  
(corresponds to 
severity 3) 
kV  2 (line to ground), 1 (line to line) 
  Electrostatic discharge acc. to 
IEC 61000-4-2  
(corresponds to severity 3) 
kV  8 (air discharge), 6 (contact discharge) 
  Field-related interference 
suppression to IEC 61000-4-3  
(corresponds to severity 3) 
V/m  10 
Electromagnetic compatibility (EMC)  
– Emitted interference 
Severity B acc. to EN 55011 (CISPR 11) and 
EN 55022 (CISPR 22) 
Resistance to extreme climates - 
Humidity 
%  95 
Dimensions  See Dimension drawings (dimensions in mm) (Page 552) 
Installation altitude above sea level  m  Up to 2,000 
Mounting position Any 
Type of fixing  Direct mounting/stand-alone assembly with terminal support 
1)
  Permissible rated current in the case of heavy-duty starting S0 at 10 to 40 A: 
- CLASS 20, I
emax
 = 32 A, 
- CLASS 30, I
emax
 = 25 A 
2) 
  Signaling contact 97/98 in "tripped" position: 4/11 g/ms