SIRIUS 3RR2 current monitoring relays 
  8.8 Operation 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
715 
Navigation in the menu  
There are basically two ways of navigating in both menus: 
●  Press and release the shift key (≤ 500 ms) 
Within a menu, you can jump from one parameter to the next by pressing and releasing 
the shift key. The sequence - which is fixed - is shown in the table below. 
 
Entry  Display in the RUN menu  Display in the SET menu 
1.  Current measured value or error symbol, 
switching contact symbol, and monitoring 
method for diagnostics 
Hysteresis 
2.  Threshold value for current undershoot for 
the CO contact 31-32-34 
ON-delay time 
3.  Threshold value for current overshoot for 
the CO contact 31-32-34 
Tripping delay time 
4.  Threshold value for current undershoot for 
the semiconductor output Q  
Reclosing delay time 
5.  Threshold value for current overshoot for 
the semiconductor output Q 
Blocking current monitoring  
6.    Fault current monitoring  
7.    Memory (automatic/manual RESET)  
8.    Incorrect phase sequence monitoring  
9.    Load current monitoring (apparent 
current/active current) 
10.    Functional principle (closed-circuit 
principle/open-circuit principle) 
●  Press and hold down the shift key (> 2.5 s) 
Press and hold down the shift key to switch from the RUN menu to the SET menu and 
vice versa.  
–  RUN → SET 
You can switch menus from any of the parameters. While the shift key is pressed 
down, "SET?" is displayed. 
When you switch menus, you are always taken to the "Hysteresis" menu command in 
the "SET" menu.  
In the event of an error you will only be able to switch to the "SET" menu from the 
"RUN-Settings" 
②. 
–  SET → RUN 
You can switch menus from any of the menu commands. While the shift key is 
pressed down, "RUN?" is displayed and the changes to the settings are applied.  
When you switch menus, you are always taken to the "Current measured value" 
parameter in the RUN menu.  
 
 
 
Note 
Aborting the menu switchover 
The switchover process will be interrupted if the shift key is released while "SET?" or 
"RUN?" is displayed. The menu will revert to the menu command you were working 
with when the switch was initiated.