Examples of Circuit Diagrams
WARNING
Automatic Motor Restart.
Can cause death, serious personal injury or property damage.
Do not use automatic reset mode when unexpected automatic restart of the motor can occur and cause injury to persons or damage
to equipment.
The Start command (e.g. via the PLC) must be canceled before a Reset command is given, since an automatic restart is executed after
the Reset command when the Start command is still pending. This applies in particular in the case of motor protection tripping. For
safety reasons, it is recommended to integrate the group fault output (terminals 95 and 96) into the controller.
F3 = optional semiconductor fuse
1)
Permitted values for main and control voltage, see technical data.
Q1
L3
L2
L1
G1
K1
F3
L1
L2
L3
T1 T2 T3
M1
NSB0_01495
V1U1 W1
M
PE
3~
3/N/PE 400 V AC , 50 Hz
1)
(optional
semiconductor
fuse)
Main circuit, option 1:
Standard switching with optional main contactor
13 14 23 24 33 34 95 9896
+
T1 T2IN4IN3IN2IN1L-L+A1
A2
N
PE
PE
G1
K1
NSB0_01496
Motor right
Trip Reset
F2
+24 V DC
MStart Reset
L1 1/N/PE 230 V AC , 50 Hz
1)
PLC outputs
PLC inputs
No action
PS 1
No action
Switch-on duration
No action No action
Group action
PTC type A /
Thermoclick
Control circuit, option 1:
Activation of an optional main contactor
as well as activation via PLC
Rotation reversal in
inside delta circuit
M
V1
W1
U2
U1
W2 V2
G1
M1
NSB0_01497
L1 L2 L3
T1 T2 T3
Q1
F3
K1
PE
3~
L3
L2
L1 3/N/PE 400 V AC , 50 Hz
1)
Main circuit, option 2:
Inside delta circuit
13 14 23 24 33
34
95 98
96
+
T1 T2IN4
IN3
IN2IN1
L-
L+
A1
A2
N
PE
PE
G1
NSB0_01498
Trip Reset
Control circuit, option 2
Activation via PLC
+24 V DC
MStart Reset
F2
L1 1/N/PE 230 V AC , 50 Hz
1)
PLC outputs
PLC inputs
Switch-on
duration
No action Group fault
No action
PS 1
No action
No action
PTC type A
Thermoclick
Motor right
G1
L1 L2 L3
T1 T2 T3
M1
NSB0_01499
M
V1
U1
W1
U2
W2 V2
PE
3~
Q1
L3
L2
L1 3/N/PE 400 V AC , 50 Hz
1)