External circuitry
10.2 Typical circuits
3TK2826 safety relay
48 Manual, 08/2007, GWA NEB 926 1579-02 DS 02
Table 10-15 Circuit example 13: NC and NO contacts without cross-circuit detection, with monitored
start
• Without cross-circuit detection
• NC contact + NO contact
• 2-channel
• Monitored start
• 3TK2826-.BB4.
DIP switch
1 2 3 4 5 6 7 8
0 0 1 — 1 — — —
Category in accordance with DIN
EN ISO 13849-1
3
Y12 T1 Y33 T3 1
Y22 T2 Y34
START
9'&
A1
A2
M
K
1
K
n
.
.
.
Safety Integrity Level (SIL),
in accordance with IEC 61508
2
Table 10-16 Circuit example 14: NC and NO contacts without cross-circuit detection, with autostart
• Without cross-circuit detection
• NC contact + NO contact
• 2-channel
• Autostart
• 3TK2826-.BB4.
DIP switch
1 2 3 4 5 6 7 8
0 0 1 — 0 0 — —
Category in accordance with DIN
EN ISO 13849-1
3
Y12 T1 Y33 T3 1
Y22 T2 Y34
9'&
A1
A2
M
K
1
K
n
.
.
.
Safety Integrity Level (SIL),
in accordance with IEC 61508
2