Technical data
6.2 Output
SITOP PSU100S
44 Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
6EP1322-2BA00 6EP1323-2BA00
Duration of the overload
capability, overcurrent / for a
short circuit while powering up
Remark
800 ms
once-only
800 ms
once-only
Short-time overload current / for
a short circuit in operation /
typical
26 A 48 A
Duration of the overload
capability, overcurrent / for a
short circuit in operation
Remark
800 ms
once-only
800 ms
once-only
Can be connected in parallel to
increase the power rating
Yes
Number of devices that can be
connected in parallel to increase
the power rating, units
2
Output characteristic see diagram, output
characteristic for 6EP1322-
2BA20 (Page 46)
see diagram, output
characteristic for 6EP1323-
2BA20 (Page 46)
Capacitive load, max. 2 mF/A