EasyManua.ls Logo

Siemens SITOP PSU200M 6EP1333-3BA10 - Closed-Loop Control; Protection and Monitoring

Siemens SITOP PSU200M 6EP1333-3BA10
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
6.4 Closed-loop control
SITOP modular 1ph/2ph
48 Manual, 04.2018, C98130-A7548-A1-4-7629
6.4
Closed-loop control
6EP1333-3BA10
(24 V/5 A)
6EP1334-3BA10
(24 V/10 A)
6EP1336-3BA00
(24 V/20 A)
6EP1337-3BA00
(24 V/40 A)
Dyn. line regulation
(U
in rated
±15 %), max.
0.1 % 0.1 % 1 % 1 %
Dyn. load regulation
(I
out
: 50/100/50 %), U
out
±
typ.
3 % 3 % 2 % 2 %
Load step regulation time
50 to 100%, typ.
2 ms 2 ms 2 ms 2 ms
Load step regulation time
100 to 50%, typ.
2 ms 2 ms 2 ms 2 ms
Regulation time, max.
5 ms
5 ms
5 ms
5 ms
6.5
Protection and monitoring
6EP1333-3BA10
(24 V/5 A)
6EP1334-3BA10
(24 V/10 A)
6EP1336-3BA00
(24 V/20 A)
6EP1337-3BA00
(24 V/40 A)
Output overvoltage pro-
tection
< 35 V < 35 V < 35 V < 35 V
Current limitation, typ.
5.5 A
12 A
23 A
46 A
Property of the output:
short-circuit proof
Yes
Short-circuit protection
Optional constant current characteristic curve or latching shutdown
Continuous short-circuit
current: rms value, typ.
5.5 A 12 A 23 A 46 A
Overload / short-circuit
display
Yellow LED for "overload", red LED for "latching shutdown"
6.6
MTBF
6EP1333-3BA10 (24 V/5 A)
6EP1334-3BA10 (24 V/10 A)
6EP1336-3BA00 (24 V/20 A)
6EP1337-3BA00 (24 V/40 A)
Mean Time Between Fail-
ures
SN29500: > 500000 h (typ. 700000 h) at 40 °C, rated load, 24 hour operation

Related product manuals