Commissioning
6.5 Local commissioning
SITRANS LT500 with ultrasonic transducer inputs
56 Compact Operating Instructions, 02/2024, A5E52021877-AA
For more information about commissioning a Level, Space, or Distance application, go to
Quick commissioning: Level/Space/Distance (Page 57).
For more information about commissioning a Volume application, go to Quick
commissioning: Volume (Page 63).
For more information about commissioning a Volume flow application, go to Quick
commissioning: Volume flow (Page 71).
Important information regarding the use of commissioning wizard
A reset to defaults should be performed before running "Quick commissioning wizard" if
the device has been used in a previous application.
Settings for quick commissioning wizard are inter-related and changes apply only after
"Apply?" is set to 'Yes' in final step.
Do not use quick commissioning wizard to modify individual parameters.
Perform customization for your application only after "Quick commissioning wizard" has
been completed.
While the device is being configured, the output remains active and continues to respond to
changes in the process.
Quick Commissioning wizard (menu item 1.1)
The Quick commissioning wizard will guide you through configuration of parameters
essential for your application. You configure parameters essential for your application by
selecting the configuration path and sub-wizards appropriate for your application.
Step: Select application
With a dual-point device, you will be prompted to set up each point individually, otherwise
set the type of measurement required for the application.
This is done in the 'Select application' step.
The options available are:
• Level
• Space
• Distance
• Volume
• Volume flow