Commissioning
6.5 Local commissioning
SITRANS LT500 with ultrasonic transducer inputs
62 Compact Operating Instructions, 02/2024, A5E52021877-AA
Response rate
Sets reaction speed of device to measurement changes in target range.
Use a setting just faster than the maximum filling or emptying rate (whichever is faster).
0.1 m/min (fill/empty rate)
1.0 m/min (fill/empty rate)
10.0 m/min (fill/empty rate)
Alarm and limit parameters for fill and empty rates work in conjunction, and are affected by
parameter "Response rate" (set in the "Quick commissioning" wizard). The rate parameters
automatically adjust when parameter "Response rate" is altered, but any changes made to the
rate parameters following the completion of the wizard will supersede the response rate
setting. See menu Rate (2.1.8).
Material type
Used to optimize performance based on material type.
• Liquid
• Solid
This parameter does not appear in the quick commissioning wizard when the sensor type is
set to "4 ... 20 mA".
Step: Apply?
Apply?
Applies settings as last step in wizard.
Wizard completes and settings are applied.
Returned to start of wizard.