Commissioning
6.5 Local commissioning
SITRANS LT500 with ultrasonic transducer inputs
72 Compact Operating Instructions, 02/2024, A5E52021877-AA
Sensor reference point
Head
Upper calibration point
Material surface
Lower calibration point
Maximum head/Maximum flow
Zero head offset
Far range
Zero head
Setting
Description
Reference point
Volume flow
Flow rate in an open channel in Volume
flow units
Zero head, zero flow
Step: Units
Note
Local units set immediately by wizard
All local units are set immediately in wizard when "Units" step completed.
Units are an exception to the general rule for all other wizard settings: Settings for quick
commissioning wizard are inter-related and changes apply only after "Apply?" is set to
"Yes" in final step.
Units for local operation are applied even if wizard is cancelled in final step. Therefore, re-
run the wizard if a change must be made to units setting.