Commissioning
6.5 Local commissioning
SITRANS LT500 with ultrasonic transducer inputs
Compact Operating Instructions, 02/2024, A5E52021877-AA
79
Step: Primary measuring device
Primary measuring device (PMD)
Sets the type of primary measuring device (PMD) used.
Setting
Exponential devices
Rectangular flume BS 3680/ISO 4373
Round nose horizontal crest weir BS 3680/ISO 4373
Trapezoidal flume BS 3680/ISO 4373
U-flume BS 3680/ISO 4373
Finite crest weir BS 3680/ISO 4373
Thin plate rectangular weir BS 3680/ISO 4373
Thin plate V-notch weir BS 3680/ISO 4373
Rectangular weir contracted
Round pipe
Palmer-Bowlus flume
H-flume
Custom
Default
Exponential devices
If PMD is not listed, set to "Custom" and use a volume flow calculation.
Step: Method of flow calculation
Method of flow calculation
Sets method of flow calculation.
Setting
Absolute
Ratiometric
Default
Absolute
Set this parameter to "Ratiometric" only if the primary measuring device (PMD) supports
ratiometric calculations. (Note that Palmer Bowlus Flume and H-Flume support ratiometric
calculations only.)