Commissioning
6.5 Local commissioning
SITRANS LT500 with ultrasonic transducer inputs
Compact Operating Instructions, 02/2024, A5E52021877-AA
89
Step: Relays currently assigned
Relays currently assigned
Displays any relays that are currently configured for other applications, as a reference of relay
availability for the basic control function.
This step does not appear if no relays are configured for other applications.
Step: Control relays
Control relays
Enables selected relays for basic control function.
Deselecting an already programmed relay will disable it.
Setting
[ ] Relay output 1
[ ] Relay output 2
[ ] Relay output 3
[ ] Relay output 4
[ ] Relay output 5
[ ] Relay output 6
Default
[X] indicates enabled by default
[ ] indicates disabled by default
Step: On/off setpoints
Note
Step is repeated per relay
The parameters in this step will need to be set for each relay used in the application.
On setpoint relay 1
Sets the level at which the relay turns on.
Setting
-99999 ... 99999 m
Default
0.0 m
Off setpoint relay 1
Sets the level at which the relay turns off.
Setting
-99999 ... 99999 m
Default
0.0 m