SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
A5E03434645-01, 08/2011
29
Condition
All valves are closed.
Procedure
WARNING
The transmitter should not be depressurized if toxic substances are being used.
To commission the transmitter with liquids, proceed as follows:
1. Open both the shut-off valves
at the pressure tapping point.
2. Open the stabilizing valve
.
3. With transmitters below the differential pressure transducer, open both the drain valves one after the other
until the
air-free liquid emerges.
In the case of a transmitter above the differential pressure transducer, open both the vent valves one after the other
until the liquid emerges.
4. Close both drain valves
or vent valves .
5. Open the differential pressure valve
and the vent valve on the positive side of the transmitter slightly, until fluid
escapes without bubbles.
6. Close the vent valve.
7. Open the vent valve on the negative side of the transmitter
slightly, until fluid escapes without bubbles.
8. Close the differential pressure valve
.
9. Open the differential pressure valve
until the liquid emerges and then close it.
10. Close the vent valve on the negative side of the transmitter
.
11. Open the differential pressure valve
by rotating it in half a turn.
12. Check and if required adjust the zero point (4 mA) if the start-of-scale value is 0 bar.
13. Close the stabilizing valve
.
14. Open the differential pressure valves (
and ) completely.