Note
Electromagnetic compatibility (EMC)
You can use this device in industrial environments, households and small businesses.
For metal housings there is an increased electromagnetic compatibility compared to high-
frequency radiation. This protection can be increased by grounding the housing, see Technical
data (Page 199).
Note
Improvement of interference immunity
Lay signal cables separate from cables with voltages > 60 V.
Use cables with twisted wires.
Keep device and cables at a distance from strong electromagnetic fields.
Take account of the conditions for communication specified in the Technical data
(Page 199).
Use shielded cables to guarantee the full specification according to HART/PA/FF/Modbus/
EIA-485/Profibus DP.
6.2 Connecting the device
6.2.1 Opening the device
Safety catch (optional)
Cover of the electrical cable compartment.
Figure 6-2 Rear view of pressure transmitter
Connecting
6.2 Connecting the device
SITRANS P320/P420 with 4 to 20 mA/HART
68 Operating Instructions, 11/2019, A5E44852162-AC

Table of Contents

Other manuals for Siemens SITRANS P320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITRANS P320 and is the answer not in the manual?

Siemens SITRANS P320 Specifications

General IconGeneral
Accuracy±0.065% of span
Temperature Range-40 to 85 °C (-40 to 185 °F)
Long-term Stability±0.1% of URL per 5 years
CommunicationHART, PROFIBUS PA, FOUNDATION Fieldbus
Output Signal4 to 20 mA HART, PROFIBUS PA, or FOUNDATION Fieldbus
Process Connection1/2" NPT, G1/2, 1/4" NPT
Ingress ProtectionIP66
DisplayOptional LCD display
Housing MaterialStainless steel, aluminum
SIL SuitabilitySIL 2/3
Power Supply10.5 to 45 V DC