SITRANS TH/TR/TF
A5E32520693-01, 06/2013
27
Table 7-2 Measured variable: Ohmic resistance
SITRANS TH200/TH300, TR200/TR300
Input type
Resistance, potentiometer
Linear to resistance or special characteristic curve
Resistance 0 ... 390 5 -
Table 7-3 Measured variable: Temperature
SITRANS TH200/TH300, TR200/TR300
Sensor type (thermo pairs)
● Type B
Pt30Rh-Pt6Rh according to DIN IEC 584
+100 ... +1820
100 (180) +400 ... +1820
W5%-Re according to ASTM 988
0 ... +2300
100 (180) 0 ... +2300
● Type D
W3%-Re according to ASTM 998
0 ... +2300
100 (180) 0 ... +2300
NiCr-CuNi according to DIN IEC 584
-200 ... +1000
(-328 ... +1832)
50 (90) -100 ... +1000
(-148 ... +1832)
● Type J
Fe-CuNi according to DIN IEC 584
-210 ... +1200
50 (90) -100 ... +1000
NiCr-Ni according to DIN IEC 584
-230 ... +1370
(-382 ... +2498)
50 (90) -100 ... +1200
(-148 ... +2192)
● Type L
Fe-CuNi according to DIN 43710
-200 ... +900
50 (90) -200 ... +900
● Type N
NiCrSi-NiSi according to DIN IEC 584
-200 ... +1300
50 (90) -180 ... +1300
Pt13Rh-Pt according to DIN IEC 584
-50 ... +1760
100 (180) -50 ... +1760
● Type S
Pt10Rh-Pt according to DIN IEC 584
-50 ... +1760
100 (180) -50 ... +1760
Cu-CuNi according to DIN IEC 584
-200 ... +400
40 (72) -200 ... +400
● Type U
Cu-CuNi according to DIN 43710
-200 ... +600
50 (90) -200 ... +600
Cold junction compensation
● Internal
With integrated resistance thermometer Pt100
With external Pt100 IEC 60751 (two-wire or three-wire connection)
● External fixed
Cold junction temperature can be set as fixed value