95
TUTORBIT
COSMOGAS
6 - USE
Alarm cong N/A
Installer 0x01FC (?...?)
Alarm delay Delay between the alarm and it being signalled
Installer 0...3600 0 s
Contact function Contact function normally open or closed
Installer NO...NC NO
Circuit 2 RT Same menu as for “Circuit 1 RT”
Installer
Circuit 3 RT Same menu as for “Circuit 1 RT”
Installer
Circuit 4 RT Same menu as for “Circuit 1 RT”
Installer
Circuit 5 RT Same menu as for “Circuit 1 RT”
Installer
Circuit 6 RT Same menu as for “Circuit 1 RT”
Installer
Enab DHW Same menu as for “Circuit 1 RT”
Installer
Alarm input Heat Pump Same menu as for “Circuit 1 RT”
Installer
Software info
User
Boiler Cascade Software version and date
User
Main page
User
Day Date Time
User
State 100% 100% 100% 100% State of the heat generators intended as Stb = stand-by or percentage of 0-10V signal received
User
Cascade S 100°C M 100°C Cascade sensor setting S = Setpoint temperature; M = Measured temperature
User
1 OFF S 100°C M 50°C Heating circuit 1 state and setting: ANF = Antifreeze; Stb = stand-by; ON = heat demand; OFF = circuit off; S
= Setpoint temperature; M = Measured temperature
User Heating circuit 1 state
2 OFF S 100°C M 50°C Heating circuit 2 state and setting: ANF = Antifreeze; Stb = stand-by; ON = heat demand; OFF = circuit off; S
= Setpoint temperature; M = Measured temperature
User Heating circuit 2 state
3 OFF S 100°C M 50°C Heating circuit 3 state and setting: ANF = Antifreeze; Stb = stand-by; ON = heat demand; OFF = circuit off; S
= Setpoint temperature; M = Measured temperature
User Heating circuit 3 state
4 Stb 60°C M 63°C Heating circuit 4 state and setting: ANF = Antifreeze; Stb = stand-by; ON = heat demand; OFF = circuit off; S
= Setpoint temperature; M = Measured temperature
User Heating circuit 4 state
DHW OFF 100°C DHW circuit state and setting: ANL = Anti-legionella; Stb = stand-by; ON = heat demand; OFF = circuit off;
Temperature measured by the domestic hot water tank sensor
User
State and temperature measured by the DHW
sensor (when present)
Solar OFF 100°C Solar circuit state and setting: ANF = Antifreeze; ASG = Anti-stagnation; Stb = stand-by; ON = heat demand;
OFF = circuit off; Temperature measured by the solar panel sensor
User
State and temperature measured by the solar panel
sensor
“ESC” key pressed quickly: If you are viewing the synoptic screen, go to the main menu. If you are at any step within the menu, go back without saving.
“ESC” key pressed for 2sec. (Only valid for HMI POL895)
HMI settings Remote control settings
User
V10.50 B0122
User
Backlight colour
User Blue...White Blue
Backlight timed switch-off
User 0...300 0
Contrast
User 0...60 60
Brightness
User 0...100 100
Firmware update
User Yes...No No