Maximum load voltage 250 V AC/30 V DC
Maximum load current
8 A @ 250 V AC
5 A @ 24 V DC
20k cycles (resistive)
Operate time Maximum: 10 ms
Release time Maximum: 5 ms
Lifetime
No Load: 10,000,000 operations
Rated Voltage and Load: 50,000 operations
Number 8
Type
Externally excited, 24 V DC whetting voltage available from
the meter
Reference voltage 40 V
Event timestamp accuracy ± 1 ms
Maximum voltage
30 V AC
60 V DC
Pulse frequency ≤ 25 Hz
Response time 1 cycle
Minimum pulse width 20 ms
Current draw
ON: ≤ 2.5 mA
OFF: ≤ 0.5 mA
Voltage ON state
4–30 V AC
4–60 V DC
Voltage OFF state
0–1.4 V AC
0–2.0 V DC
IRIG-B
IRIG-B00x format (unmodulated IRIG-B time code)
Coded expressions 0–7 are supported but the year data is
not used.
Digital inputs
Output voltage 24 V DC
Output current 20 mA
Maximum load 8 digital inputs (meter base)
Whetting source (Digital inputs)
9810 series - User manual 9810 specifications
7EN05-0390-08 294