Bulk charging voltage
(C.V voltage)
48V mode: default 56.4V, 48.0V~58.4V Settable
24V mode: default 28.2V, 24.0V~29.2V Settable
12V mode: default 14.1V, 12.0V~14.6V Settable
If “Li” is selected ,it can’t be set up
Floating charging
voltage
48V mode: default 54.0V, 48.0V~58.4V Settable
24V mode: default 27.0V, 24.0V~29.2V Settable
12V mode: default 13.5V, 12.0V~14.6V Settable
If “Li” is selected ,it can’t be set up
48V mode: default 42.0V, 40.0V~48.0V Settable
24V mode: default 21.0V, 20.0V~24.0V Settable
12V mode: default 10.5V, 10.0V~12.0V Settable
48V Li model: default 20%,5%~50% Settable
SIG (default), used to communicate with upper computer
CL1, used to communicate through RS485
CL2, used to communicate through CAN.
RS485
Communication
Address
Protocol 1 (default)
Used to communicate with controller in CL1 or CL2, or used to
communicate with upper computer in SIG
If ”Flooded” or ”User-Defined” is selected in program this program can
be set up.