14 Charger Power Source
Priority
Solar and Utility (Default)
14 Charger Power Source
Priority
Solar Only
15 Alarm On/Off Control
Audible Alarm on (default)
15 Alarm On/Off Control
Audible Alarm off(Mude)
16 Backlight On/Off
Control
Backlight on (default)
16 Backlight On/Off
Control
Backlight off
When off is set, the LCD will go dim
after 60 seconds left unattended.
17 Beeps once between AC
and DC Transfer
Alarm on (default)
17 Beeps once between AC
and DC Transfer
Alarm off
19 C.V. Charging Voltage
48V model: default 56.4V,
48.0V~58.4V Settable
20 Float Charging Voltage
21 Low Battery Cut-Off
Voltage
Without BMS communication
21 Low Battery Cut-Off
Voltage
With BMS communication
22 RS485
Communication Address
Default 001. 001-255 Settable. For
external solar charger expansion.
23 Battery Equalization
Disabled (Default)
23 Battery Equalization
Enable
24 Battery Equalization
Voltage
Default 58.4V, 48~60V settable