PV Charge Initiation Condition
Batter voltage > 30Vdc & PV voltage must be at least 5 volts higher than battery voltage.
DC Input
Low DC Cut-Off Voltage (For Lead Acid)
36-52V Adjustable
Low DC Warning Voltage (For Lead Acid)
Low DC Cut-off Voltage +2Vdc
Low DC Warning Return Voltage
(For Lead Acid)
>48V
Low DC Warning SOC (For Li)
Low DC Cut-off Soc +5%
Low DC Warning Return SOC (For Li
Low DC Cut-off Soc +15%
Low DC Cut-off SOC (For Li)
Default 20%, 5%~50% Adjustable
Cold Start Battery Minimal Voltage
Lead Acid: Low DC Cut-Off Voltage+2Vdc | Lithium >Low DC Cut-off Soc+10%
High DC Recovery Voltage
58VDC
High DC Cut-Off Voltage
AGM:60V, FLD:62V, USE or Li Mode: C.V. Voltage + 4.0V (Fault After 60 seconds)
AC INPUT
Nominal Voltage
240VAC
Bypass Voltage Range
Appliance Mode: 154~272Vac±5V / 164~262Vac±5V(Recover)
UPS Mode: 184~272Vac±5V / 194~262Vac±5V(Recover)
Utility Charge Voltage Range
Appliance Mode: 154V-260Vac / 164V-250Vac(Recovery)
UPS Mode: 184V-260Vac / 194-250Vac(Recovery)
Frequency Range
45-65Hz/ (47-63Hz Recovery)
Maximum Charge Current
40A
50A
60A
70A
80A
100A
BYPASS & PROTECTION
Grid & Generator
Typical Transfer Time
10ms
Overload Protection (SMPS Load)
Circuit breaker
Output Short Circuit Protection
Circuit breaker
AC Input Breaker
63A
63A
63A
80A
80A
80A
AC output Breaker
32A
32A
32A
63A
63A
63A
MECHANICAL SPECIFICATIONS
Unit Dimensions (W*H*D)
540*360*218mm / 21.2*14.2*8.6”
650*380*225mm / 25.6*15*8.9”
Packing Size (W*H*D)
740*550*460mm / 30*21*18
810*540*410mm / 31.9*21.3*16.1”
Net Weight
38kg/84lbs
41kg/90lbs
45kg/99lbs
64kg/141lbs
66kg/145lbs
75kg/165lbs
Gross Weight
53kg/116lbs
55kg/121lbs
61kg/135lbs
84kg/185lbs
86kg/190lbs
95kg/210lbs
OPERATING ENVIRONMENT
Operation Temperature Range
-20°C to 50°C/ -4°F to 122°F
Storage Temperature
-20°C to 60°C / -4°F to 140°F
Nominal Altitude
<1000m. The output will be de-rated by about 5% with altitude increase of every 500 meters.
Appendix 2: M Series Inverter/Charger System Wiring
Diagram

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sigineer Power M6048D and is the answer not in the manual?

Sigineer Power M6048D Specifications

General IconGeneral
BrandSigineer Power
ModelM6048D
CategoryInverter
LanguageEnglish

Related product manuals