EasyManua.ls Logo

Sime FORMAT 34I BF - 3 INSTALLING THE BOILER; 3.1 FIXING THE WALL MOUNTING BRACKET; 3.2 HANGING THE BOILER; 3.3 FLUE DUCTS MODEL 341 BF

Sime FORMAT 34I BF
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C12
C32
C42
3
1
2
7
6
4
3
2
min 1,3 m - max 5 m
8
x
y
x + y = max 3,5 m "25"
x + y = max 3,0 m "30-35"
max 3,5 m "25"
max 3,0 m "30-35"
8
APPLIANCE PACKAGE:
- boiler (assembled);
- installation and servicing instructions;
- users instructions;
- wall mounting bracket;
- fixing screws with wall plugs.
3.1 FIXING THE WALL MOUNTING BRACKET
Before installing the appliance ensure that the chosen loca-
tion is suitable (section 2.2) and that the requirements for
flue position, (section 2.3), and minimum clearances, (
Table 2
)
are satisfied.
These minimum clearances are essential to provide access
for servicing, and are included on the wall mounting tem-
plates.
Open the paper wall mounting templates. If a rear flue is
to be used, discard the side templates and secure the
rear template in the desired position. For a side flue appli-
cation, secure both the rear and appropriate side tem-
plate in position.
Mark the position of the two wall mounting bracket fixing
holes and the flue/air duct hole on the appropriate wall(s).
Remove the template(s) and drill the two fixing holes using
a 10 mm masonry drill. Fit the plastic plugs provided.
Cut the hole in the wall for the flue/air duct. The diame-
ter should not be less than 100 mm (4 in) and must be
horizontal. Refer to fig. 12-14.
Accurately measure the wall thickness, and note this
dimension for later use.
Secure the wall mounting bracket in position using the
screws provided. Ensure that it is the correct way up, as
indicated in fig. 6.
3.2 HANGING THE BOILER
Lift the appliance into position. The upper cross member
locates onto the wall mounting bracket.
Screw in the wall mounting bracket adjusting screws until
the appliance is secure and vertical.
3.3 FLUE DUCTS MODEL “34I BF”
The air inlet-smoke outlet assembly ø 60/100 is supplied in a
kit code 8084811 complete with mounting instructions.
With the curve supplied in the kit the maximum horizontal
length of the flue must not exceed 3 metres.
When the extension code 8086908 is used, the end of
the flue must always have a horizontal outlet.
The diagrams in fig. 7 illustrate a number of examples of dif-
ferent coaxial outlets.
3 INSTALLING THE BOILER
Fig. 6
KEY
1 Wall mounting bracket
2 Plastic wall plug (2 Off)
3 Woodscrew (2 Off)
4 Washer (2 Off)
5 Adjustment screw (2 Off)
KEY
1 Coaxial flue kit code 8084811
2 a Extension L. 1000 code 8096100
2 b Extension L. 500 code 8096101
3 Vertical extension L. 200 code 8086908
4 Additional 90° curve code 8095800
6 Articulated tile code 8091300
7 Roof outlet terminal L. 1284 code 8091200
8 Vertical condensation collector L. 200 code 8092803
Fig. 7
IMPORTANT:
Each additional 90° curve installed reduces
the available length by 0.90 metres.
Each additional 45° curve installed reduces
the available length by 0.45 metres.
It is advisable to assemble the condensation
collector (8) on vertical segments exceeding
2.5 metres in length and to limit maximum
length to 4 metres.
max 3 m
min. 1,3 m - max. 3 m

Related product manuals