Details the use of projected photoelectric beam smoke detection for large areas and the Simplex 2098-9207A's microprocessor-based design.
Specifies the operating voltage range for the detector, typically 18 to 32 VDC.
Details the maximum coverage distance for the beam, ranging from 30 ft to 350 ft.
Outlines the available sensitivity delay settings, including 30-second and 5-second options.
Provides ratings for auxiliary contacts for Alarm, Trouble, and Auxiliary Alarm signals.
Specifies the operational temperature limits for the unit, from 32°F to 130°F (0°C to 54°C).
Guidance on mounting height from smooth, flat, or sloped/peaked ceilings for optimal beam path.
Advice on potential issues with air stratification affecting smoke detection and recommendations.
Instructions to avoid direct sunlight or bright artificial lights interfering with the receiver.
Ensuring a clear line-of-sight path, avoiding moving objects and airflow disturbances.
Reminder of the ambient temperature limits for proper operation of the detector unit.
Describes the remote panel providing LED indications for Alarm, Trouble, and Power-On.
Specifies mounting needs for the panel, including a single-gang switch box and minimum depth.
Details the use of projected photoelectric beam smoke detection for large areas and the Simplex 2098-9207A's microprocessor-based design.
Specifies the operating voltage range for the detector, typically 18 to 32 VDC.
Details the maximum coverage distance for the beam, ranging from 30 ft to 350 ft.
Outlines the available sensitivity delay settings, including 30-second and 5-second options.
Provides ratings for auxiliary contacts for Alarm, Trouble, and Auxiliary Alarm signals.
Specifies the operational temperature limits for the unit, from 32°F to 130°F (0°C to 54°C).
Guidance on mounting height from smooth, flat, or sloped/peaked ceilings for optimal beam path.
Advice on potential issues with air stratification affecting smoke detection and recommendations.
Instructions to avoid direct sunlight or bright artificial lights interfering with the receiver.
Ensuring a clear line-of-sight path, avoiding moving objects and airflow disturbances.
Reminder of the ambient temperature limits for proper operation of the detector unit.
Describes the remote panel providing LED indications for Alarm, Trouble, and Power-On.
Specifies mounting needs for the panel, including a single-gang switch box and minimum depth.