Features 
Individually addressable manual fire alarm 
stations with: 
 Power and data supplied via IDNet or MAPNET II
addressable communications using a single wire pair
 Operation that complies with ADA requiremen
ts
 Visible LED indicator that flashes during
communications and is on steady when the station has
been activated
 Th
e NO GRIP Single Action Station and Retrof
it Kit
are available with a more easily operated pull lever for
applications where anticipated users may find the
standard station lever difficult to activate
 Pul
l lever that protrudes when alarme
d
 Break-rod supplied (use is optional)
 Models are available with single or double action
(breakglass or push) operation
 UL listed to Standard 38
Compatible with the following Simplex
®
 control 
panels: 
 Model Series 4007ES, 4008, 4010, 4010ES, 4100
ES,
4100U, 4020, 4100, and 4120 fire alarm control
panels equipped with either IDNet or MAPNET II
communications
 Model Series 2120 Communicating Device
Transponders (CDTs) equipped with MAPNET II
communications
Compact construction: 
 Electronics module enclosure minimizes dust
infiltratio
n
 Allows mounting in standard electrical boxes
 Screw terminals for wiring connections
Tamper resistant reset key lock 
(keyed same as 
Simplex fire alarm cabinets) 
Multiple mounting options: 
 Surface or semi-flush with standard boxes or matching
Simplex boxes
 Flush mount adapter kit
 Adapters are available for retrofitting to commonly
available existing boxes
Description 
The Simplex addressable manual station combines the 
familiar Simplex manual station housing with a compact 
communication module that is easily installed to satisfy 
demanding applications. Its integral individual 
addressable module (IAM) constantly monitors status and 
communicates changes to the connected control panel via 
IDNet or MAPNET II communications wiring.  
* Refer to page 2 for specific model listings. This product has been approved by the 
California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health 
and Safety Code. See CSFM Listing 7150-0026:224 for allowable values and/or conditions 
concerning material presented in this document. Additional listings may be applicable; 
contact your local Simplex product supplier for the latest status. Listings and approvals 
under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. 
4099-9004 
Single action 
4099-9021 
NO GRIP 
Single action 
4099-9805 
NO GRIP 
Retrofit kit 
ALARMFIRE
PULL    DOWN
PUSH
ALARMFIRE
KEY
OPERATED
ONLY
ALARMFIRE
KEY
OPERATED
ONLY
4099-9005 
Breakglass 
4099-9006 
Push 
With 2099-9828 
Institutional  
Cover kit 
Operation 
Activation of the 4099-9004 single action manual station 
requires a firm downward pull to activate the alarm switch. 
Completing the action breaks an internal plastic break-rod 
(visible below the pull lever, use is optional). The use of a 
break-rod can be a deterrent to vandalism without 
interfering with the minimum pull requirements needed for 
easy activation. The pull lever latches into the alarm 
position and remains extended out of the housing to provide 
a visible indication. 
Single Action NO GRIP Station 4099-9021. For 
applications such as California Building Code, Title 24, 
which requires “Controls and operating mechanisms shall 
be operable with one hand and shall not require tight 
grasping, pinching or twisting of the wrist” the model 
4099-9021 station provides a more easily operated pull 
lever compared to standard stations. Retrofit of existing 
stations is available using the 4099-9805 Retrofit kit.  
Double Action Stations (Breakglass) require the 
operator to strike the front mounted hammer to break the 
glass and expose the recessed pull lever. The pull lever then 
operates as a single action station. 
Double Action Stations (Push Type) require that a 
spring loaded interference plate (marked PUSH) be pushed 
back to access the pull lever of the single action station. 
Station reset requires the use of a key to reset the manual 
station lever and deactivate the alarm switch. (If the break-
rod is used, it must be replaced.) 
Station testing is performed by physical activation of the 
pull lever. Electrical testing can be also performed by 
unlocking the station housing to activate the alarm switch.
Multi-Application Peripherals
 
UL, ULC, CSFM Listed; IDNet or MAPNET II Communicating Devices 
FM Approved *  Addressable Manual Stations 
S4099-0005  10/2014