Page 17 579-1102 Rev H
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
5 IDNAC power supply
An IDNAC power supply is used in the 4007ES panel, the non-hybrid panel. It provides 4 A and can support the following:
Addressable notification devices.
Addressable initiating devices.
See Figure 15: IDNAC power supply on page 17 and Table on page 17 for the main components of the IDNAC power supply.
Fig 15: IDNAC power supply
Table 12: Main components information
P1 RUI Class A/B jumpers P2 IDNet Class A/B jumper
TB4 Battery connection TB2 IDNAC
P10 AC Power Connection TB3 Aux Relay 1 and 2
J15
DCAI
Zone/Relay Connection
J10 IDNet Loop 2
J7 Zone/Relay J11 IDNet Loop 3
J16 CPU Connection P5 Battery Depleted Jumper
J17 Option Connection P8 1-2 (default) / IDNet card on line
P11 City Circuit Connection
TB1 IDNet Loop 1, Aux Power, RUI Connection
P9
25V Regulator Jumpers 1-2, 3-4
default. Power is fed to the zone/relay card. No jumpers.