Service Port    Page 1
REPORT 10  TrueAlertES Self-Test Report  12:34:56pm   MON  01-JUN-15
Point ID  Custom Label  Date  Visual  Audible 
T1-1-1  VO FIRST FLOOR (up to 40 characters
1
UN
5
O OUT 
/A
T1-2-5  AV FIRST FLOOR EAST WING 
1
UN
5
O OUT 
ORMAL
T7-3-55  AO SECOND FLOOR EAST WING
1
UN
5
/A 
O OUT
T8-2-45  AV SECOND FLOOR ROOM 29 
1
UN
5
OT TST 
/A
T8-2-60  AV SECOND FLOOR ROOM 22 
1
UN
5
ORMAL 
ORMAL
T1-2-4  AO FIRST FLOOR ROOM 17 
1
UN
5
/A 
NSUPP
TRUEALERT_ES SELF-TEST REPORT COMPLETED 
 
 
Press RETURN for next Screen OR CTRL-X to abort 
 
Results Description: 
NORMAL = works correctly 
NO OUT = No Output, no light or sound was detected 
NOT TST = no result; either the appliance did not return a result before the test ended or the test was conducted as silent (strobes 
only) and audible appliance was not activated 
N/A = not applicable (no strobe on audible only, etc.) 
UNSUPP = appliance not compatible with Self-Test (TrueAlert addressable appliance not TrueAlert ES addressable appliance) 
Note: Additional TrueAlert ES Self-Test information is detailed in Operating Instructions 579-1165 shipped with the panel. 
Service Port    Page 1
REPORT 10  TrueAlertES Self-Test Report  12:34:56pm   MON  01-JUN-15
Point ID  Custom Label  Date  Visual  Audible 
T1-1-1  VO FIRST FLOOR 
1
UN
5
O OUT 
/A
T1-2-5  AV FIRST FLOOR EAST WING 
1
UN
5
O OUT 
ORMAL
T1-2-6  AV FIRST FLOOR NORTH ENTRANCE
2
AY
O OUT 
ORMAL
T7-3-55  AO SECOND FLOOR EAST WING
1
UN
5
/A 
O OUT
T8-2-45  AV SECOND FLOOR ROOM 29 
1
UN
5
OT TST 
/A
T1-1-11  AV FIRST FLOOR SOUTH ENTRANCE
2
AY
5
ORMAL 
ORMAL
T8-2-60  AV SECOND FLOOR ROOM 22 
1
UN
5
ORMAL 
ORMAL
T1-2-4  AO FIRST FLOOR ROOM 17 
1
UN
5
/A 
NSUPP
T1-2-7  AO FIRST FLOOR ROOM 12 
2
AY
5
/A 
NSUPP
T8-3-43  AV SECOND FLOOR ROOM 25 
2
AY
5
NSUPP 
NSUPP
TRUEALERT_ES SELF-TEST REPORT COMPLETED 
 
 
Press RETURN for next Screen OR CTRL-X to abort 
 
CUSTOM LABEL   
4-1-2 AV 
POINT ADDRESS: 4-1-2  Type: AV 
CARD: 4     CHANNEL: 1    DEVICE: 2 
EXTENDED POWER SUPPLY 
UNIT NUMBER: 2 
RUI NUMBER: LOCAL 
PRIMARY STATUS  NORMAL 
AUDIBLE GROUP CONFIG:  0 0 0 
VISUAL GROUP CONFIG:   0 0 0  
STYLE:   INDOOR 
OPERATION:   GENERAL EVAC 
CANDELA RATING  15 CD 
COLOR LENS  YES 
TONE TYPE  BROADBAND 
CODING TYPE  TEMPORAL 
VOLUME HIGH 
LAST TEST TIME:  MON 01-JUN-15  01:00 AM 
LAST VISUAL TEST:  NORMAL 
LAST AUDIBLE TEST:  NORMAL 
LAST TEST VOLUME:  NORMAL 
DEVICE TEST TROUBLE:   NORMAL 
 TrueAlert ES Appliance Self-Test Last Test Results Report Example 
 TrueAlert ES Appliance Self-Test All Test Results Report Example 
 TrueAlert ES Appliance Self-Test Individual Appliance Report Example