7  S4007-0002-6  11/2015
Input Power 
120 VAC Input  2 A maximum @ 102 to 132 VAC, 50/60 Hz 
240 VAC Input  1 A maximum @ 204 to 264 VAC, 50/60 Hz 
Battery  6 A maximum @ 24 VDC (during battery operation) 
4007ES Power Supply 
Output Ratings 
Power Supply 
Output Rating 
4 A output for “Special Application” appliances 
Note: The 4 A output rating was determined such that 
optional module currents, and external device and appliance 
currents can be directly added together, not to exceed 4 A 
total. 
Output switches to 
battery backup 
during mains AC 
failure or brownout 
conditions 
IDNAC SLC Ratings  
3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit 
loads; DC-DC converter circuit is >92% efficient over 
operating range 
IDNAC SLC Wiring 
Output terminals are rated for 18 to 12 AWG with duplicate 
output terminals rated for two wires each, allowing up to four 
(4) Class B branch circuit T-taps to be made in the cabinet; 
additional T-taps may be made in external wiring junction 
cabinets or boxes 
Auxiliary Power Tap  2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC) 
Compatible Special Application Appliances 
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact 
your Simplex product representative for compatible appliances 
Battery Charger 
Ratings 
(sealed lead-acid 
batteries) 
Battery capacity range 
UL and ULC listed for battery charging of 6.2 Ah up to 33 Ah (batteries larger than 
18 Ah require a remote battery cabinet) 
Charger characteristics 
and performance 
Temperature compensated, dual rate, recharges depleted batteries within 48 hours 
per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527 
Custom Background Display Details 
Supported file types: JPG, BMP, GIF, and PNG 
Recommended image type is JPG, recommended image size is 480 x 240, and the 
file size limit is 100 kb 
Environmental 
Operating Temperature  32° to 120°F (0° to 49° C) 
Operating Humidity   Up to 93% RH, non-condensing @ 90° F (32° C) maximum 
Additional Technical Reference 
Description Document Description Document 
Installation Manual  579-1102  Single Page Operator Instructions  579-1109 
Zone/Relay Module Installation Manual  579-1103  4007ES Hybrid Data Sheet   S4007-0001 
Detailed Operator’s Manual  579-1165   
Field Installed Optional Modules 
Model  Description  Supv.  Alarm 
4190-8001*  TrueInsight Remote Service Gateway Module and Programming Selection 
Required 
Selection 
62 mA  73 mA 
4190-6106 * 
TrueInsight Remote Service Gateway Module Installation Kit; includes module and 
harness; configured for dynamic IP address operation unless ordered with 4190-4016 
4190-4016 * 
TrueInsight Remote Service Gateway Module for fixed IP Addressing; optional, select if application will use fixed IP 
address
 
* Refer to data sheet S4100-0063 for additional TrueInsight Service Gateway details 
Batteries 
Model   Capacity  Battery Mounting Details 
2081-9272 6.2 Ah 
12 V Batteries for cabinet mounting; select one battery model per system standby requirements; order quantity 
of two; to be wired in series for 24 VDC 
2081-9274 10 Ah 
2081-9288 12.7 Ah 
2081-9275 18 Ah 
2081-9287  25 Ah  For remote mount in Battery Box 4009-9801 
Batteries for remote mounting; see battery cabinet details 
below 
2081-9276  33 Ah  For remote mount in Battery Box 4009-9802 
Battery Accessories 
Model  Color  Capacity  Dimensions  Description 
4009-9801 Beige 
For up to 25 Ah 
batteries 
16 ¼” W x 13 ½” H x 5 ¾” D 
(413 mm x 343 mm x 146 mm) 
External battery cabinet without charger, with locking 
solid door and battery harness; for close-nippled 
mounting to fire alarm control panel cabinet 
4009-9802 Beige 
For up to 33 Ah 
batteries 
25 ¾” W x 20 ¾” H x 4 ” D  
(654 mm x 527 mm x 105 mm) 
Accessories 
Model  Description 
2080-9047  DACT cable, 14 ft (4.3 m) long, RJ45 plug one end, spade lugs on the other; order one per phone line connection required 
2975-9812  Red semi-flush box trim; 1 
7
⁄
16
” (37 mm) wide, four corners and trim pieces for top, bottom, and sides 
2975-9813  Platinum semi-flush box trim; 1 
7
⁄
16
” (37 mm) wide, four corners and trim pieces for top, bottom, and sides 
4081-9018 10 k, 1 W end-of-line resistor harness for Class B non-addressable initiating zones (if 4007-9801 is used) 
2081-9031 
Series resistor for WSO, non-addressable IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before 
tamper) 470 , 1 W, encapsulated, two 18 AWG leads (0.82 mm
2
 ), 2 ½” L x 1 ” W x 1” H (64 mm x 35 mm x 25 mm) 
 Module and Accessories Selection Information (Continued) 
 General Specifications