Setting Switches
Switch SW1 is a bank of eight DIP switches. From left to right (see Figure 1) these switches are designated as SW1-1 through SW1-8. The function of
these switches is as follows:
SW1-1. This switch sets the baud rate for the serial communication line running between the Relay Daughter card and the Panel CPU. Set this
switch to ON.
SW1-2 through SW1-8. These switches set the card's address within the 4100 FACP. (These switches must be set to the value assigned to the
card by the Panel Programmer.) Refer to Figure 2 for a complete list of the switch settings for all of the possible card addresses.
Figure 1: Address DIP Switch
4" X 5" card DIP switches
4100-3204
4100-3206
4010-9908
Daughter card DIP switches
4100-3001
4100-3201
4100-3002
4100-3202
4120-3003
4100-3203
page 3 579-220 Rev. F
4100/4120- Series and 4010ES Relay Modules Installation Instructions

Other manuals for Simplex 4010ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010ES and is the answer not in the manual?

Simplex 4010ES Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Operating Temperature32°F to 120°F (0°C to 49°C)
Power Supply120V AC or 240V AC
Zones10
Communication PortsRS-232, Ethernet
Signaling Line Circuits (SLCs)2
Notification Appliance Circuits (NACs)4
Max Notification AppliancesVaries based on NAC configuration and power supply
Communication OptionsCellular, Ethernet
Weight30 lbs
Humidity RangeUp to 93% non-condensing
CertificationsUL, FM, CSFM, MEA
Network CapabilityYes

Related product manuals