Constant Supervision NAC (CSNAC) Wiring
See note 1
See note 2
See note 3. See note 3.
See note 4. See note 4.
Figure 9: CSNAC Wiring
Note:
1.  4081-9008
2.  4081-9018
3.  4100-1259
4.  4100-1260
Note:
•  Leave the 10 K resistors on the "B+" and "B-" terminals of unused circuits.
•  Remove the 10 K resistors from the "B+" and "B-" terminals on the card that hosts the CSNAC (amplifiers and XSIG cards).
•  All wiring is between 18 AWG (0.8231 mm
2
) (minimum) to 12 AWG (3.309 mm
2
) (maximum).
•  Field wiring is power-limited.
•  The maximum speaker circuit current is 2 A per circuit.
•  The total available alarm power is 100 W (4 A @ 25 VRMS, 1.414 A @ 70.7 VRMS) or as limited by the connected amplifier.
•  Shields, when required, are normally connected as shown. Alternate shield termination using earth ground is provided on the amplifier chassis.
•  Signal wiring must test free of grounds.
•  70V CSNAC circuits require Unshielded Twisted Pair (UTP) cable.
•  The maximum combined capacitance of all CSNAC speaker circuit wiring to each amplifier:
-  100W 25V: 1.3uF
-  100W 70V: 0.15uF
•  Consult your local Simplex Office if installing a 70V CSNAC system with more than 6000ft of total wire to any single amplifier. Additional
equipment may be needed.
•  For guidance regarding proper wiring practice when using TrueAlert ES speaker appliances, refer to the Speaker Wiring Application Guidelines
in the ES-PS IDNAC Card Installation Instructions, 579-1289.
page 12 579-174  Rev. Q
Digital/Analog Amplifiers Installation Instructions