EasyManua.ls Logo

Simplex 4100-1314 - Page 12

Simplex 4100-1314
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Constant Supervision NAC (CSNAC) Wiring
See note 1
See note 2
See note 3. See note 3.
See note 4. See note 4.
Figure 9: CSNAC Wiring
Note:
1. 4081-9008
2. 4081-9018
3. 4100-1259
4. 4100-1260
Note:
Leave the 10 K resistors on the "B+" and "B-" terminals of unused circuits.
Remove the 10 K resistors from the "B+" and "B-" terminals on the card that hosts the CSNAC (amplifiers and XSIG cards).
All wiring is between 18 AWG (0.8231 mm
2
) (minimum) to 12 AWG (3.309 mm
2
) (maximum).
Field wiring is power-limited.
The maximum speaker circuit current is 2 A per circuit.
The total available alarm power is 100 W (4 A @ 25 VRMS, 1.414 A @ 70.7 VRMS) or as limited by the connected amplifier.
Shields, when required, are normally connected as shown. Alternate shield termination using earth ground is provided on the amplifier chassis.
Signal wiring must test free of grounds.
70V CSNAC circuits require Unshielded Twisted Pair (UTP) cable.
The maximum combined capacitance of all CSNAC speaker circuit wiring to each amplifier:
- 100W 25V: 1.3uF
- 100W 70V: 0.15uF
Consult your local Simplex Office if installing a 70V CSNAC system with more than 6000ft of total wire to any single amplifier. Additional
equipment may be needed.
For guidance regarding proper wiring practice when using TrueAlert ES speaker appliances, refer to the Speaker Wiring Application Guidelines
in the ES-PS IDNAC Card Installation Instructions, 579-1289.
page 12 579-174 Rev. Q
Digital/Analog Amplifiers Installation Instructions

Related product manuals