Features 
 
IDNet expansion module for 4100ES fire alarm 
control panels: 
  Provides 250 IDNet device point control including 
both QuickConnect and QuickConnect2 sensors 
  Extends the 4100ES QuickConnect and 
QuickConnect2 sensor sensitivity to seven levels of 
adjustment from 0.2% to 3.7% 
  Requires a single block (4” x 5”) module location 
  Also compatible with 4100U systems 
Intended for upgrade of Simplex
®
 4010 fire alarm 
control panels: 
  Allows for system expansion beyond 250 addressable 
points, up to the 2500 point capacity of the 4100ES 
control panel 
  Systems can retain the installed QuickConnect and/or 
QuickConnect2 sensors 
  Additional IDNet SLC (Signaling Line Circuit) 
channels are available from 4100ES standard or 
expansion IDNet modules 
UL Listed to Standard 864 
Description 
 
4010 System Upgrade. The Simplex model 4010 fire 
alarm control panel provides for up to 250 addressable 
points using IDNet communications. One of the 4010 
unique devices is the QuickConnect sensor. 
QuickConnect sensors provide TrueAlarm analog 
sensing in a feature optimized package, primarily suited to 
smaller systems. The original QuickConnect sensor has been 
replaced with the QuickConnect2 sensor. 
When a facility expands beyond the capacity of the 
4010 control panel, the preferred upgrade is the 4100ES fire 
alarm control panel. Standard 4100ES IDNet signaling line 
circuits (SLCs) are not compatible with QuickConnect 
sensors. However, with the 4100-3106, all of the 4100ES 
compatible IDNet devices and the QuickConnect and 
QuickConnect2 sensors can be connected to the same fire 
alarm control panel.  
Expanded Sensitivity Range. Additionally, the 4100ES 
with the 4100-3106 module can provide a full range of 
sensitivity for the QuickConnect sensors with seven levels 
of adjustment from 0.2% to 3.7%. Standard sensitivities are 
1.5%, 2.0%, 2.5%, and 3.7%. Sensitivities of 0.2%, 0.5%, 
and 1% are for special applications in clean areas. (For 
detailed application information including sensitivity 
selection, refer to Installation Instructions 574-709.) 
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to 
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:251 
for allowable values and/or conditions concerning material presented in this document. It is 
subject to re-examination, revision, and possible cancellation. This product was not approved 
by MEA (NYC) as of document revision date. Additional listings may be applicable, contact 
your local Simplex product supplier for the latest status. Listings and approvals under 
Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. 
 
ALARMFIRE
PULL    DOWN
SIM PLEX TI M E RECO RDER CO.
4090-9002
RELAY IAM
INSTAL.  INSTR.  574-184
DATE CODE:
1
5
6
7
8
1
2
3
4
Addressable station
Monitor ZAMs 
and Relay IAMs
Supervised IAM
QuickConnect
TrueAlarm sensor
Modular TrueAlarm 
sensor with base
Modular TrueAlarm sensor 
with IDNet isolator base
To additional IDNet 
devices, up to 250 total
POWER
BEFORE
 SERVICING
CAUTION
DISCONNECT
  4009  IDNet   NAC  EXTENDER
TM
4009 IDNet NAC 
Extender
New 2500 point 4100ES 
Fire Alarm Control Panel 
QuickConnect2
TrueAlarm sensor
Original Facility 
Requirements
Facility Expansion 
Requirements
Original 250 point 
4010 Fire Alarm 
Control Panel 
To additional IDNet 
devices, up to 250 
total per IDNet SLC
4100-3106 IDNet module 
with QuickConnect 
Sensor Support
IDNet SLC 
channel for 
standard devices
 
4010 System Expansion using a 4100-3106 IDNet Module 
4100-3106 Specifications 
 
Capacity 250 points 
Standby 
Current 
with 250 devices  275 mA 
without devices  75 mA 
per device  0.8 mA 
Alarm 
Current 
with 250 devices  265 mA 
without devices  115 mA 
per device  1 mA 
Operating Temperature 
Range 
32 F to 120 F (0 C to 49 C) 
Humidity Range 
Up to 93% RH, non-condensing 
@ 90° F (32° C) 
Mounting 
Single 4100ES block; 4” x 5” 
(102 mm x 127 mm) 
Installation Instructions  574-800 
 
 
Fire Control Panels
 
UL, ULC, CSFM Listed;  4100-3106 IDNet Expansion Module with 
FM Approved*  QuickConnect/QuickConnect2 Sensor Compatibility  
    S4100-0039-4  2/2014