Do you have a question about the Simplex TrueAlarm 4008-9102 and is the answer not in the manual?
Brand | Simplex |
---|---|
Model | TrueAlarm 4008-9102 |
Category | Control Panel |
Language | English |
Features operator convenience with LCD, LEDs, PC access for configuration, and custom labels.
Supports up to 200 addressable TrueAlarm detection or device points via IDNet.
Two Class A or B NACs rated 2A each, with SmartSync or synchronized strobe control.
3A @ 24 VDC output, auto-selects 120/240 VAC input, and charges batteries.
Includes programmable reminders, auxiliary relays, power-limited circuits, and UL listing.
Modules include door annunciator, expansion power supply, and city interface.
Panels for up to 200 addressable devices and 4 NACs, offering flexible control and LCD labels.
IDNet SLC supports up to 200 addressable devices, including TrueAlarm sensors.
Class A/B NACs with electronic control, synchronized strobe or SmartSync operation.
Provides 500mA @ 24 VDC aux output and two programmable relay outputs.
Supports Contact ID, SIA, 3/1, 4/2, BFSK formats with auto 24-hour test.
Provides 3A @ 24 VDC, additional NACs, and three programmable relays.
Modules for remote station or municipal master reporting, with or without disconnects.
Lists panel and option module part numbers with descriptions for selection.
Details trim kits, battery cabinets, and required 12V batteries for system installation.
IDNet devices use TrueAlarm sensors for addressable detection, monitoring smoke chamber condition.
Photoelectric sensitivity at 2.5%/ft; heat detectors offer fixed temp and rate-of-rise.
Details the main panel display, status indicators, and their functions during operation.
Explains the alphanumeric keypad and navigation keys for programming and control.
Monitors detector dirtiness and sensitivity, fulfilling NFPA 72 requirements.
Allows detector head types to be interchanged without panel reprogramming.
Lists compatible detector heads (photoelectric, heat) and addressable bases with data sheets.
Details addressable duct detector housings and various addressable modules.
Includes Voice Control Panels, Remote NAC Extenders, and various annunciator types.
Details features of 4610-9111 LED/Switch and 4606-9101 LCD Annunciators.
Details AC input voltage/current and DC power supply output and battery charger ratings.
Ratings for NACs including 2A per NAC, Class A/B, and strobe synchronization.
Specifies 500mA auxiliary output and 2A relay ratings for various operations.
Covers IDNet device support, wiring, distances, and annunciator communication parameters.
Details module ratings and the environmental operating parameters for the system.
Lists supervisory and alarm current draw for control panels, expansion supplies, and annunciators.
Details photoelectric and heat detectors, including options for bases and sensitivity settings.
Defines function types for addressable devices like FIRE, WATER, HEAT, DUCT, PULL, SMOKE.
Lists various NAC modes including signal types, SmartSync, and utility signals.
Defines relay operations for fire alarms, supervisory, trouble, and special functions.
Covers custom label creation, message library use, and system history log management.
Details autoprogramming, alarm group configuration, WALKTEST, and manual control.
Defines the four-tier passcode protection levels for system access and programming.
Provides cabinet dimensions, knockout locations, and semi-flush mounting guidelines.
Illustrates placement for main board, display assembly, AC input, and optional modules.
Explains the 14 custom label areas and dual LED indicators for status tracking.
Describes the function of the four yellow LEDs for default NAC trouble annunciation.