Simplex TrueAlarm 4008-9102 User Manual

Simplex TrueAlarm 4008-9102
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Features
Control panel operator convenience features:
Wide viewing angle 2 x 20 (40 character) alphanumeric
LCD and dedicated LEDs provide convenient panel
status information
Operation is programmable using a multi-function
keypad and the panel LCD or via service computer (PC)
RS-232 service port provides upload/download PC
access for panel configuration and event history logs
Software updates are via PC download
Convenient library of standard custom label terms
Standard on-board DACT provides: Contact ID, 3/1, 4/2,
BFSK, and SIA formats
WALKTEST silent or audible system test
Voltage and current for both the battery charger and the
battery can be displayed at the front panel LCD
Addressable Devices:
Using IDNet communications, up to 200 addressable
TrueAlarm detection points or addressable device points
are available (see page 3 for details)
Two Standard Notification Appliance Circuits (NACs):
Class A or Class B outputs with solid state overcurrent
protection per NAC, each rated for 2 A
Selectable for Simplex
®
SmartSync two-wire
horn/strobe control or synchronized strobe control
Standard Power Supply:
Provides 3 A maximum @ nominal 24 DC
Automatic input power selection operates with 120 VAC
or 240 VAC, 50 or 60 Hz
On-board temperature compensated battery charger for
up to 12.7 Ah batteries in cabinet (UL and ULC) and up
to 25 Ah batteries in separate cabinet (UL only)
Additional standard features:
Programmable Active Status Reminder
Two auxiliary relays
NACs, Relay outputs, and communications circuits
are power limited (AC input, battery circuits, and City
Circuit Module outputs are non-power limited)
Available with beige or red cabinet
UL listed to Standard 864
Available option modules:
Door mounted 24 LED annunciator (standard on ULC
models)
3 A Expansion Power Supply with two on-board 2 A
NACs that operate the same as standard NACs
City Interface Module and Auxiliary Relay Module
Remote LCD and LED/Switch Annunciators
ALARM
ACK
SUPV
ACK
TROUBLE
ACK
ALARM
SILENCE
SYSTEM
RESET
FIRE
ALARM
SYSTEM
SUPERVISORY
SYSTEM
TROUBLE
ALARM
SILENCED
AC
POWER
CAUTION
DISCONNECT
BATTERY AND
A. C. POWER
BEFORE
SERVICING
4008-9102 (Beige) Standard Control Panel
ALARM
ACK
SUPV
ACK
TROUBLE
ACK
ALARM
SILENCE
SYSTEM
RESET
FIRE
ALARM
SYSTEM
SUPERVISORY
SYSTEM
TROUBLE
ALARM
SILENCED
AC
POWER
Fire Alarm Annunciator
CAUTION
DISCONNECT
BATTERY AND
A. C. POWER
BEFORE
SERVICING
4008-9122 (Beige) Control Panel with 24 LED Annunciator
(required for ULC applications)
Description
For areas requiring up to 200 addressable input devices and
up to 4 NACs, the Simplex 4008 Series fire alarm control
panels provide flexible initiating circuit monitoring,
extensive programmable control capability, and LCD
annunciated circuit-specific 20 character custom labels.
* See page 2 for additional ULC and MEA information. This product has been approved by
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California
Health and Safety Code. See CSFM Listing 7165-0026:318 for allowable values and/or
conditions concerning material presented in this document. It is subject to re-examination,
revision, and possible cancellation. Additional listings may be applicable, contact your local
Simplex product supplier for the latest status. Listings and approvals under Simplex Time
Recorder Co. are the property of Tyco Fire Protection Products.
TrueAlarm Addressable Fire Alarm Control Panels
UL, ULC, CSFM Listed; FM Approved; 4008 Fire Alarm Control Panel for IDNet Addressable
MEA (NYC) Acceptance* Devices and TrueAlarm Addressable Smoke Detection
S4008-0001-8 8/2012
Question and Answer IconNeed help?

Do you have a question about the Simplex TrueAlarm 4008-9102 and is the answer not in the manual?

Simplex TrueAlarm 4008-9102 Specifications

General IconGeneral
BrandSimplex
ModelTrueAlarm 4008-9102
CategoryControl Panel
LanguageEnglish

Summary

Simplex TrueAlarm Addressable Fire Alarm Control Panel Features

Control Panel Operator Convenience

Features operator convenience with LCD, LEDs, PC access for configuration, and custom labels.

Addressable Device Support

Supports up to 200 addressable TrueAlarm detection or device points via IDNet.

Notification Appliance Circuits (NACs)

Two Class A or B NACs rated 2A each, with SmartSync or synchronized strobe control.

Standard Power Supply and Battery Charger

3A @ 24 VDC output, auto-selects 120/240 VAC input, and charges batteries.

Additional Standard Features

Includes programmable reminders, auxiliary relays, power-limited circuits, and UL listing.

Optional Expansion Modules

Modules include door annunciator, expansion power supply, and city interface.

Simplex 4008 Series Panel Description

System Overview and Capabilities

Panels for up to 200 addressable devices and 4 NACs, offering flexible control and LCD labels.

Simplex 4008 Control Panel Standard Features

IDNet Addressable Operation

IDNet SLC supports up to 200 addressable devices, including TrueAlarm sensors.

On-Board Notification Appliance Circuits

Class A/B NACs with electronic control, synchronized strobe or SmartSync operation.

Auxiliary Power and Relay Outputs

Provides 500mA @ 24 VDC aux output and two programmable relay outputs.

On-Board Digital Alarm Communicator Transmitter (DACT)

Supports Contact ID, SIA, 3/1, 4/2, BFSK formats with auto 24-hour test.

Simplex 4008 Control Panel Optional Features

Expansion Power Supply and Relay Module

Provides 3A @ 24 VDC, additional NACs, and three programmable relays.

City Circuit Modules

Modules for remote station or municipal master reporting, with or without disconnects.

Simplex 4008 Product Selection and Accessories

Control Panel and Option Module Models

Lists panel and option module part numbers with descriptions for selection.

Mounting Accessories and Batteries

Details trim kits, battery cabinets, and required 12V batteries for system installation.

Simplex TrueAlarm Smoke Detection Technology

Addressable Detection Principles

IDNet devices use TrueAlarm sensors for addressable detection, monitoring smoke chamber condition.

Sensitivity and Alarm Determination

Photoelectric sensitivity at 2.5%/ft; heat detectors offer fixed temp and rate-of-rise.

Simplex 4008 Control Panel Keyboard and Interface

Panel View, LCD Readout, and Status LEDs

Details the main panel display, status indicators, and their functions during operation.

Keypad Functions and Navigation Keys

Explains the alphanumeric keypad and navigation keys for programming and control.

Simplex 4008 Diagnostics and Detector Features

Status Monitoring and Detector Diagnostics

Monitors detector dirtiness and sensitivity, fulfilling NFPA 72 requirements.

Modular Detector/Base Interchangeability

Allows detector head types to be interchanged without panel reprogramming.

Simplex 4008 Compatible Peripherals and Modules

Detector Heads and Addressable Bases

Lists compatible detector heads (photoelectric, heat) and addressable bases with data sheets.

Addressable Duct and System Devices

Details addressable duct detector housings and various addressable modules.

System Expansion Panels and Annunciators

Includes Voice Control Panels, Remote NAC Extenders, and various annunciator types.

Remote Annunciator Options and Features

Details features of 4610-9111 LED/Switch and 4606-9101 LCD Annunciators.

Simplex 4008 Fire Alarm Control Panel Specifications

Power Input and Output Specifications

Details AC input voltage/current and DC power supply output and battery charger ratings.

Notification Appliance Circuit (NAC) Specifications

Ratings for NACs including 2A per NAC, Class A/B, and strobe synchronization.

Auxiliary Outputs and Relay Specifications

Specifies 500mA auxiliary output and 2A relay ratings for various operations.

IDNet and Annunciator Communication Details

Covers IDNet device support, wiring, distances, and annunciator communication parameters.

Option Modules and Environmental Ratings

Details module ratings and the environmental operating parameters for the system.

Simplex 4008 Supervisory and Alarm Current Draw

Current Consumption for Panels and Modules

Lists supervisory and alarm current draw for control panels, expansion supplies, and annunciators.

Simplex 4008 Addressable Device Information

Addressable Fire Detection Devices

Details photoelectric and heat detectors, including options for bases and sensitivity settings.

Addressable Hardware Point Types

Defines function types for addressable devices like FIRE, WATER, HEAT, DUCT, PULL, SMOKE.

Simplex 4008 NAC and Relay Operation Modes

NAC Operation Modes Overview

Lists various NAC modes including signal types, SmartSync, and utility signals.

Relay Operation Modes and Special Functions

Defines relay operations for fire alarms, supervisory, trouble, and special functions.

Simplex 4008 Additional Programming Features

Custom Labels, Message Library, and History Logs

Covers custom label creation, message library use, and system history log management.

Autoprogram, Alarm Groups, and System Testing

Details autoprogramming, alarm group configuration, WALKTEST, and manual control.

Passcode Protection and Access Levels

Defines the four-tier passcode protection levels for system access and programming.

Simplex 4008 Installation and Module Placement

Cabinet Dimensions and Installation Knockouts

Provides cabinet dimensions, knockout locations, and semi-flush mounting guidelines.

Internal Module Placement Reference

Illustrates placement for main board, display assembly, AC input, and optional modules.

Simplex 4008 Door LED Annunciator Details

Custom Label Areas and LED Indicators

Explains the 14 custom label areas and dual LED indicators for status tracking.

Default NAC Trouble Annunciation LEDs

Describes the function of the four yellow LEDs for default NAC trouble annunciation.

Related product manuals