6 S4008-0001-8 8/2012
Model Module Supervisory Alarm
4008-9101
4008-9102
Standard fire alarm control panel 135 mA + 0.8 mA per IDNet device 190 mA + 1 mA per IDNet device
4008-9121
4008-9122
Control panel with 24 LED Annunciator 153 mA + 0.8 mA per IDNet device 240 mA + 1 mA per IDNet device
4008-9801 Expansion Power Supply 50 mA 60 mA
4008-9802 Expansion Relay Module 10 mA per energized relay 10 mA per energized relay
4006-9805
City Circuit Module with disconnect
switch
30 mA 60 mA
4006-9806
City Circuit Module without disconnect
switch
30 mA 60 mA
4606-9101
Remote LCD Annunciator (see data
sheet S4606-0001)
65 mA 140 mA
4610-9111
Remote LED/Switch Annunciator (see
data sheet S4610-0001)
40 mA
70 mA
(all LEDs and tone-alert on)
** Current Calculation Information:
1. To determine total supervisory current, add currents of modules in panel to base system value and all auxiliary loads.
2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads
and all auxiliary loads.
Available Fire Detection Device Types
Device Description Options
Photoelectric
Addressable
Detector
TrueAlarm operation with
sensitivity = 2.5%/ft
Sounder base (selectable
for single station operation)
With communications isolator
With relay output
Selectable for all detectors to be at city of
Boston sensitivity of 3.7%/ft
Heat Detector
Fixed temperature thermal
detection at 135° F (57.2° C)
Sounder base (selectable
for single station operation)
With communications isolator
With relay output
Individually selectable to add rate-of-rise heat
detection of 15° F/minute (8.3° C/minute)
Photoelectric
Detector with
Heat Detector
Combination detector, dual address base with options available per above
Addressable Hardware Point Types
Function Type Description Function Type Description
FIRE Fire monitor device WSO Combination waterflow and water supervisory device
WATER Waterflow monitor device SUPV Supervisory monitor
HEAT Heat detector device UTIL Supervised utility monitor
DUCT Duct detector device TROUBLE Trouble monitor
PULL Manual (pull) station device VSMOKE
Verified fire alarm; an alarm level causes the alarm
verification cycle to start
SMOKE Smoke detector device STYLEC Style C fire monitor
SO Sprinkler Supervisory LATSUPV
Latching supervisory monitor (supervisory latches
until system is reset)
IAM
Individual Addressable
Module
ISOL Addressable Isolator
MBZAM Class B addressable IDC monitor module
SIGNAL Signal IAM MAZAM Class A addressable IDC monitor module
RIAM Addressable Relay ADRPUL Addressable manual station
Addressable Device Information
The following addressable device types and hardware point types are provided. A combination of autoprogram, and either
front panel or PC programming allows the operation to be selected per application.
Supervisory and Alarm Currents