5 S4008-0001-8 8/2012
AC Input
Input Voltage 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select
Input Current, Standard 2 A maximum @ 120 VAC input; 1.5 A maximum @ 240 VAC input
Input Current with
Expansion Power Supply
4 A maximum @ 120 VAC input; 3 A maximum @ 240 VAC input
Power Supply Output 3 A maximum @ 24 VDC in alarm
Battery Charger
Temperature compensated charger is rated for up to 25 Ah per UL 864; up to
12.7 Ah per ULC-S527
Notification Appliance Circuits (NACs) (NOTE: Total DC current = 3 A maximum per power supply)
General Rating
2 A maximum @ 24 VDC, per NAC; available as Class A or Class B;
Class B end-of-line resistor = 10 k, ½ W; Model 4081-9008 (P/N 733-894)
Special Application Rating = 2 A per NAC
Strobe synchronization is UL listed across all
four system NACs for these 4906 Series
appliances
Simplex 4901 Series (horns) and 4906 Series Multi-Candela non-addressable
strobes, horn/strobes, and speaker/strobes (contact your Simplex product
representative for compatible appliances)
Regulated 24 VDC Rating = 1.5 A per NAC
NOTE: Maximum strobe
load on main power
supply or expansion power supply is 1.35
A
per power supply (2.7 A total); remainder of
power supply rating is available for other
loading
Power for other UL listed appliances; use associated external synchronization
modules where required
Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum per power supply)
Auxiliary Power Output 500 mA maximum @ 24 VDC
Standard Auxiliary Relay Outputs
Relay 1 Programmable operation
Contacts rated 2 A @ 30 VDC, 0.35 power factor;
jumper selectable as N.O. or N.C.
Relay 2 Trouble operation
Wiring Connections Terminals rated for 18 AWG to 12 AWG (0.82 mm
2
to 3.31 mm
2
)
IDNet Communications
Quantity Up to 200 addressable devices (see list on page 4)
Suppression
For wiring external to building, use Overvoltage Protector 2081-9044 at each end
of the connection; refer to data sheet S2081-0016 for details
Wire Size 18 AWG (0.82 mm
2
)
Wire Types
Unshielded twisted pair (UTP)
Acceptable for most applications; not for use with wiring in conduit with either NAC
or AC power wiring (or similar)
Shielded twisted pair (STP)
Shielded wire may provide protection from unexpected sources of interference and
may be required for some applications; review system with your local Simplex
product supplier
Distance from Control Panel to Farthest
Device
Up to 4000 feet (1219 m) with 125 devices; 32
Up to 2500 feet (762 m) with 200 devices; 51
Total Wire Length Allowed With “T” Taps for
Class B Wiring
Up to 10,000 ft (3 km)
Total Capacitance Allowed 0.6 µF (600 nF)
Annunciator Communications
Quantity Supported Up to four annunciator modules per panel (see page 4 for details)
Wiring Size and Type See description for IDNet wiring above
Wiring Distances
Bus-Style Wiring Up to 4000 ft (1219 m); 0.58 µF (580 nF) maximum capacitance; 35 max.
“T-Tap” Wiring Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device
Line Matching Resistor
Bus-Style Wiring Connect one at panel and one at end of line
100 , ½ W; 4081-9011;
(part number 733-974)
“T-Tap” Wiring Connect one at panel and one at farthest device
Suppression
Use 2081-9044 Overvoltage Protectors where wiring leaves and enters a building
(refer to data sheet S2081-0016)
Option Module Ratings
Expansion Relay
Module 4008-9802
Contact Ratings 2 A @ 30 VDC, 0.35 power factor; jumper selectable as N.O. or N.C.
Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm
2
to 3.31 mm
2
)
Environmental Ratings
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range Up to 93% RH, non-condensing @ 100.4° F (38° C) maximum
Specifications (Refer to Installation Instructions 579-716 for additional information)