Setting the Address
1.  The MX Digital Loop Card Address is set through a Dual-In-Line Package (DIP) 
switch SW100, which is a bank of eight switches. From left to right these switches 
are designated as SW100-1 through SW100-8 (see Figure 4). Their functions are as 
follows:
•   SW100-1: This switch sets the baud rate for the internal communications line running 
between the MX Digital Loop card and the CPU. Set this switch to ON.
•   SW100-2 through SW100-8: These switches set the card address within the Fire Alarm 
Control Panel (FACP). Refer to Table 2 for a complete list of switch settings for all of 
the possible module addresses.
Note: Set these switches to the value assigned to the MX Digital Loop card by 
the 4100ES Programmer.
Setting the 
MX Loop Card 
Address
Step 2: Configuring the MX Digital Loop Card
Figure 4. DIP Switch SW100
LT0638  Iss 1.1  7/2017  6
Use DIP Switches SW100-2 through
SW100-8 to set the Module Address.
This figure shows an Address of 3.
4100 Comm. Baud Switch
(SW100-1) must be set to ON
Position 8 is LSB
(least significant bit)
ON
OFF
OFF = ACTIVE
1    2   3    4    5    6    7   8 
Programming
The MX Digital Loop Card is programed using the 4100ESi Programmer. Refer to 
LT0619 4100ESi Programming Manual for details.