DC Inverter Duct Type Air Conditioner Installation and Operation Manual
47
The following table recommended by the model selection manual is about how to select the air switch and
power cable.
Warning! :
The section area of cables selected by users must not be smaller than the specications shown in the table
below.
Table.10
Model
Power
Supply
Capability of Air
Switch(A)
(Outdoor/Indoor)
Minimum Sectional Area
Of Earth Wire (mm
2
)
(Outdoor/Indoor)
220-240V
~
50Hz
ASD-18AIA 20/6 4.0/1.0
ASGE-18AIA WK
ASD-24AIA 20/6 4.0/1.0
ASGE-24AIA WK
ASD-36AIA 25/6 4.0/1.0
ASGE-36AIA WK
ASD-36AIA
380-415V
3N
~
50Hz
16/6 2.5/1.0
ASGE-36AIA-3 WK
ASD-42AIA 16/6 2.5/1.0
ASGE-42AIA-3 WK
Note: The parameters of the power cord listed above are only applicable to the BV single-core power cord
which is laid within the plastic bushing and used at 40°C, and those of the air switch are applicable to the one
which also is used at 40°C. If the actual installation conditions changes, please refer to the instructions of the
power cord and the air switch.