User Manual of A90 Series Inverter
190
Precautions for setting:
★
The start and stop in multi-segment speed operation depends on the function code
F00.02.
★
The acceleration/deceleration time in multi-segment speed operation can be
controlled by the external terminal with the acceleration/deceleration time
function.
The direction of multi-segment speed operation is controlled by the terminals F/R and
RUN.
0: stop after a single run
1: stop after a limited number
of cycles
2: run at the last segment
after a limited number of
cycles
3: continuous cycles
In addition to the multi-segment speed mode, it also has the simple PLC function.
There are four running modes in total, as detailed in Table 7-11.
Table 7-11 Details of PLC Running Mode
The inverter will be stopped after running in the last segment.
The inverter will run cyclically and be stopped after the set cycles. The number
of cycles depends on the function code F08.16.
The inverter will run cyclically and keep the speed of the last segment after
running in the last segment, until a stop command is received. The number of
cycles depends on the function code F08.16.
The inverter will continue cyclic operation until a stop command is received.