EasyManuals Logo

Sinee A90 Series User Manual

Sinee A90 Series
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
User Manual of A90 Series Inverter
104
proportional gain
ACR-P2
F14.51
Torque current
integral time constant
ACR-T2
0.00-600.00
0.00: no integral
ms
10.00
F14.52
Position loop gain
0.000 - 40.000
1.000
F14.53
SVC zero-frequency
processing
0: braking
1: not processed
2: seal the tube
2
F14.54
SVC zero-frequency
braking current
50.0-400.0 (100.0 is the no-load
current of the motor)
%
100.0
F14.55
SVC low-frequency
excitation current
50.0-150.0 (100.0 is the no-load
current of the motor)
%
100.0
F14.56
Voltage feedforward
gain
0 - 100
%
0
F14.77
Acceleration/decelera
tion time options of
motor 2
0: the same as motor 1
1: acceleration and deceleration
time 1
2: acceleration and deceleration
time 2
3: acceleration and deceleration
time 3
4: acceleration and deceleration
time 4
0
F14.78
Maximum frequency
of motor 2
1.00~600.00
Hz
50.00
F14.79
Upper frequency limit
of motor 2
Lower limit frequency F00.19 to
maximum frequency F14.78
Hz
50.00
F14.80
V/F curve setting of
motor 2
0: straight line V/F
1: multi-point broken line V/F
0
F14.81
Multi-point VF
frequency F1 of
motor 2
0.00 - F14.83
Hz
0.50
F14.82
Multi-point VF
voltage V1 of motor 2
0.0~100.0 (100.0 = Rated voltage)
%
1.0
F14.83
Multi-point VF
frequency F2 of
motor 2
F14.81 - F14.85
Hz
2.00
F14.84
Multi-point VF
voltage V2 of motor 2
0.0-100.0
%
4.0
F14.85
Multi-point VF
frequency F3 of
motor 2
F14.83 to rated frequency of
motor (reference frequency)
Hz
5.00