percentage is directly given, and the maximum output is 100.00%.
F09.00=4:VP
In the case of 09.00=4VP, the PID setting source is the digital potentiometer setting.
F09.00=6: communication setting
The percentage of PID setting depends directly on the communication (percentage).
If the master-slave communication (F10.05=1) is enabled and the inverter works
as the slave (F10.06=0), the specific setting percentage is “700FH (master-slave
communication setting) * F10.08 (slave receiving proportional coefficient)”, and
the 700FH data range is -100.00% to 100.00%, as detailed in Table 0-2.
For the general communication (F10.05=0), the specific setting percentage is
“7004H (communication setting of process PID setting)”, and the 7004H data
range is -100.00% to 100.00%, as detailed in Table 0-2.
Function code
Function code name
Parameter description
Unit
Default
setting
Attribute
F09.02
PID feedback source
1: AI1
2: AI2
6: Communication setting
1
F09.02=1:AI1
F09.02=2:AI2
The PID feedback percentage is directly dependent on the AI (percentage).
For the details of AI1 to AI2, see the description of F00.04. When it is used as the PID
feedback, the percentage will directly turn the feedback value, and the maximum output is
100.00%.
F09.02=6: communication setting
The PID feedback percentage is directly dependent on the communication
(percentage).
If the master-slave communication (F10.05=1) is enabled and the inverter works
as the slave (F10.06=0), the specific feedback percentage is “700FH
(master-slave communication setting) * F10.08 (slave receiving proportional
coefficient)”, and the 700FH data range is -100.00% to 100.00%, as detailed in
Table 0-2.
For the general communication (F10.05=0), the specific feedback percentage is

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sinee A90 Series and is the answer not in the manual?

Sinee A90 Series Specifications

General IconGeneral
CoolingForced air cooling
Rated Power0.4kW to 500kW
Output Voltage0 to input voltage
Output Frequency0 to 400Hz
Overload Capacity150% for 60 seconds, 180% for 10 seconds
Braking UnitBuilt-in
CommunicationModbus
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Output Voltage (AC)0 to input voltage
Output WaveformSine wave
Output Frequency (AC)0 to 400Hz
Operating Temperature-10°C to +40°C (Derating above 40°C)
Storage Temperature-20°C to 65°C
DimensionsVaries with model
WeightVaries with model