User Manual of A90 Series Inverter
77
15: length value
16: PID output percentage
18: PID feedback
19: PID setting
21: output frequency (actual
value)
22: set frequency (actual value)
23: output current (actual value)
24: output torque (actual value)
25: set torque (actual value)
27: estimated feedback frequency
(actual value)
28: synchronization frequency
(actual value)
29: acceleration and deceleration
output frequency (actual value)
F03.27
M1 output bias
-100.0~100.0
%
0.0
F03.28
M1 output gain
-10.00~10.00
1.00
F03.29
M2 output bias
-100.0~100.0
%
0.0
F03.30
M2 output gain
-10.00~10.00
1.00
F03.31
Control logic options
of PLC output
terminal
D7 D6 D5 D4 D3 D2
D1 D0
* * * * * R1 *
Y1
0: no output
1: output
00000
F04
Start/stop control parameter group
F04.00
Start-up method
0: direct start
1: start of speed tracking
0
F04.01
Start frequency
0.00~10.00
Hz
0.00
F04.02
Start frequency hold
time
0.00-60.00, 0.00 is invalid
s
0.00
F04.03
Starting current of
DC braking
0.0~100.0 (100.0 = Rated current
of motor)
%
50.0
F04.04
Starting time of DC
braking
0.00~30.00
s
0.00
F04.05
Reserved
F04.06
Pre-excitation current
50.0-500.0 (100.0 = no-load
current)
%
100.0
F04.07
Pre-excitation time
0.00~10.00
s
0.10
F04.08
Speed tracking mode
Ones place: Tracking start
frequency
0: maximum frequency
0 1