80
F05.01
Frequency point F1 of
multi-point VF
0.00~F05.03
Hz
0.50
F05.02
Voltage point V1 of
multi-point VF
0.0~100.0 (100.0 = Rated voltage)
%
1.0
F05.03
Frequency point F2 of
multi-point VF
F05.01~F05.05
Hz
2.00
F05.04
Voltage point V2 of
multi-point VF
0.0~100.0
%
4.0
F05.05
Frequency point F3 of
multi-point VF
F05.03 to rated frequency of
motor (reference frequency)
Hz
5.00
F05.06
Voltage point V3 of
multi-point VF
0.0-100.0
%
10.0
F05.07
Voltage source of VF
separation mode
0: digital setting of VF separation
voltage
1: AI1
2: AI2
3-4: retention
5: PID
6: Communication setting
7: VP
Note: 100% is the rated voltage of
the motor.
0
F05.08
Digital setting of VF
separation voltage
0.0 to 100.0 (100.0=Rated voltage
of motor)
%
0.0
F05.09
Rise time of VF
separation voltage
0.00~60.00
s
2.00
F05.10
Compensation gain of
V/F stator voltage
drop
0.00~200.00
%
100.00
F05.11
V/F slip
compensation gain
0.00~200.00
%
100.00
F05.12
V/F slip filtering time
0.00~10.00
s
1.00
F05.13
Oscillation
suppression gain
0~20000
100
F05.14
Oscillation
suppression cutoff
frequency
0.00~600.00
Hz
55.00
F05.15
Droop control
frequency
0.00~10.00
Hz
0.00
F05.16
Energy saving rate
0.00~50.00
%
0.00
F05.17
Energy saving action
time
1.00~60.00
s
5.00