7. Setting and saving parameters
The number of parameter is shown on the display, the
first line on the left (Fig. 1) The initial letter A
shows which set is displayed.
Use and buttons to browse the required
parameter. If it is not locked (key symbol), the value
of the parameter can be changed using the + or -
button. First, locked parameters must be unlocked by
typing the password, parameter A38 (Chapter 8.25.).
Press the
enter
button to save, all parameters are saved
in the memory at once. It is recommended to save in the
S-stop status.
8. Description of parameters
The controller contains a set of parameters marked
A11 - A41. Parameter numbers do not form a continuous
series of numbers for compatibility with dual controller
DIGR-2200/D.
8.1. A10
Unused parameter for this type of controller.
8.2. A11 Amplitude
Setting the value of the output voltage and the
intensity of vibrations of the feeder from 20-100% with
0.5% steps. The setting range can be restricted by the
value of parameters A17, A18 (Chapter 8.6.). The
buttons cannot be used for setting if the amplitude is
typed by AIN analogue signal (Chapter 8.11.).
8.3. A12 Timeout ON
A13 Timeout OFF
The parameters sense if at least one senor is
connected to the controller monitoring the filling of
the output storage tank of the feeder. We recommend
setting parameters to 0 s.
If the controller is in the W-wait status parts are
taken from the storage and their movement causes
a short interruption of the signal from the filling
sensor. The Timeout ON (parameter A12) must be longer
than the interruption of the signal. Then the
interruption will be ignored and the controller
switches into the R-run status after the storage tank
is discharged. The same occurs after the storage tank