38 SMC9-11TLRP-IA-en-51 Installation Manual
6 Electrical Connection SMA Solar Technology AG
Funkt.Titel_ Anforderungen an die PV-Module
Requirements for the PV modules:
All PV modules must be of the same type.
The same number of series-connected PV modules must be connected to all strings.
All PV modules must be aligned identically.
All PV modules must have the same tilt angle.
The maximum input current per string must be maintained and must not exceed the through-fault
current of the DC connectors (see section 12 "Technical Data", page 82).
The thresholds for the input voltage and the input current of the inverter must be observed
(see section 12 "Technical Data", page 82).
At an ambient temperature over 10°C, the open-circuit voltage of the PV modules must not
exceed 90% of the maximum input voltage of the inverter. That prevents the voltage exceeding
the maximum input voltage of the inverter at lower ambient temperatures.
The positive connection cables of the PV modules must be equipped with the positive DC
connectors.
The negative connection cables of the PV modules must be equipped with the negative DC
connectors.
Wichtig_Parallelschaltung mit Y-Adapter
6.4 DC Connection
6.4.1 Conditions for DC Connection
Use of Y adaptors for parallel connection of strings
The Y adaptors must not be used to interrupt the DC electric circuit.
Do not use the Y adaptors in the immediate vicinity of the inverter. The adaptors must not
be visible or freely accessible.
In order to interrupt the DC electric circuit, disconnect the inverter (see section 9).
6.4.2 Assembling the DC Connectors
Figure 13: DC connectors
Item Designation
A Negative DC connector
B Positive DC connector