Installation Manual SMC9-11TLRP-IA-en-51 61
SMA Solar Technology AG 10 Troubleshooting
CAN Internal communication fault
Corrective measures:
If this message is displayed frequently, contact the
SMA Service Line.
Check L-N-PE L and N are swapped on the AC connection or PE is not connected.
Corrective measures:
Ensure that the AC cable is correctly connected (see section
6.3.2 "Connecting the Inverter to the Electricity Grid", page 35).
If the AC cable is connected correctly and this message is still
displayed, contact the SMA Service Line.
Check Varistor At least one of the varistors is defective.
Corrective measures:
Check the function of the varistors (see section 10.8).
DC fuse At least one of the string fuses has tripped or is defective.
Corrective measures:
Check the function of the string fuses (see section 10.10).
Derating The inverter reduces its power output due to overheating.
Corrective measures:
Clean the fans .
The inverter reduces its power output because the DC input current
exceeds the maximum input current of the inverter.
Corrective measures:
Ensure that the PV plant is designed correctly.
dI-Bfr
dI-Srr
The inverter has detected a change in the differential current.
A change in the differential current can be caused by an earth fault,
residual current or a malfunction. The inverter disconnects from the
electricity grid.
Corrective measures:
If none of the above causes apply and this message is still
displayed, ensure that the PV plant is insulated correctly and that
there is no earth fault.
dl-Mess Deviation in the differential current measurement
If this message is displayed frequently, permanent shutdown will be
triggered.
Corrective measures:
Contact the SMA Service Line.